Data sheet 6ES7515-2AM01-0AB0 SIMATIC S7-1500, CPU 1515-2 PN, Central processing unit with work memory 500 KB for Program and 3 MB for data, 1st interface: PROFINET IRT with 2-port switch, 2nd interface: PROFINET RT, 30 ns bit performance, SIMATIC Memory Card required General information Product type designation CPU 1515-2 PN HW functional status FS03 Firmware version V2.6 Product function ● I&M data Yes; I&M0 to I&M3 Engineering with ● STEP 7 TIA Portal configurable/integrated as of version V15.
Type of supply voltage 24 V DC permissible range, lower limit (DC) 19.2 V permissible range, upper limit (DC) 28.8 V Reverse polarity protection Yes Mains buffering ● Mains/voltage failure stored energy time 5 ms ● Repeat rate, min. 1/s Input current Current consumption (rated value) 0.8 A Inrush current, max. 2.4 A; Rated value I²t 0.02 A²·s Power Infeed power to the backplane bus 12 W Power consumption from the backplane bus (balanced) 6.2 W Power loss Power loss, typ. 6.
● Number range 0 ... 65 535 ● Size, max. 500 kbyte ● Number range 0 ... 65 535 ● Size, max. 500 kbyte ● Size, max.
Extended retentive data area (incl. timers, counters, flags), max. 3 Mbyte; When using PS 6 0W 24/48/60 V DC HF Flag ● Number, max. 16 kbyte ● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte Data blocks ● Retentivity adjustable Yes ● Retentivity preset No Local data ● per priority class, max. 64 kbyte; max. 16 KB per block Address area Number of IO modules 8 192; max.
Clock ● Type Hardware clock ● Backup time 6 wk; At 40 °C ambient temperature, typically ● Deviation per day, max. 10 s; Typ.: 2 s Operating hours counter ● Number 16 Clock synchronization ● supported Yes ● in AS, master Yes ● in AS, slave Yes ● on Ethernet via NTP Yes Interfaces Number of PROFINET interfaces 2 1.
— Number of connectable IO Devices for RT, max. 256 — of which in line, max. 256 — Number of IO Devices that can be simultaneously activated/deactivated, max. 8; in total across all interfaces — Number of IO Devices per tool, max.
● integrated switch No ● RJ 45 (Ethernet) Yes; X2 Protocols ● IP protocol Yes; IPv4 ● PROFINET IO Controller Yes ● PROFINET IO Device Yes ● SIMATIC communication Yes ● Open IE communication Yes ● Web server Yes ● Media redundancy No PROFINET IO Controller Services — PG/OP communication Yes — S7 routing Yes — Isochronous mode No — Open IE communication Yes — IRT No — MRP No — MRPD No — PROFIenergy Yes — Prioritized startup No — Number of connectable IO Devices, max.
— MRPD No — PROFIenergy Yes; per user program — Prioritized startup No — Shared device Yes — Number of IO Controllers with shared device, max. 4 — Asset management record Yes; per user program Interface types RJ 45 (Ethernet) ● 100 Mbps Yes ● Autonegotiation Yes ● Autocrossing Yes ● Industrial Ethernet status LED Yes Protocols Number of connections ● Number of connections, max.
Web server ● HTTP Yes; Standard and user pages ● HTTPS Yes; Standard and user pages OPC UA ● Runtime license required Yes ● OPC UA client Yes — Application authentication Yes — Security policies Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 — User authentication "anonymous" or by user name & password — Number of connections, max. 10 — Number of nodes of the client interfaces, max.
— Publishing interval, min. 200 ms — Number of server methods, max. 50 — Number of inputs/outputs per server method, max. 20 — Number of monitored items, max. 2 000; for 1 s sampling interval and 1 s send interval — Number of server interfaces, max. 10 — Number of nodes for user-defined server interfaces, max. 5 000 Further protocols ● MODBUS Yes; MODBUS TCP Media redundancy ● Switchover time on line break, typ. 200 ms; For MRP, bumpless for MRPD ● Number of stations in the ring, max.
Forcing ● Forcing, variables Peripheral inputs/outputs ● Number of variables, max. 200 Diagnostic buffer ● present Yes ● Number of entries, max.
● horizontal installation, min. 0 °C ● horizontal installation, max. 60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the display is switched off ● vertical installation, min. 0 °C ● vertical installation, max. 40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the display is switched off Ambient temperature during storage/transportation ● min. -40 °C ● max.