Data Sheet
Isochronous mode
Isochronous operation (application synchronized up
to terminal)
Yes; Distributed and central; with minimum OB 6x cycle of 250 µs
(distributed) and 1 ms (central)
Equidistance Yes
S7 message functions
Number of login stations for message functions, max. 32
Program alarms Yes
Number of configurable program messages, max. 10000; Program messages are generated by the
"Program_Alarm" block, ProDiag or GRAPH
Number of loadable program messages in RUN,
max.
5000
Number of simultaneously active program alarms
● Number of program alarms
1000
● Number of alarms for system diagnostics
1000
● Number of alarms for motion technology
objects
160
Test commissioning functions
Joint commission (Team Engineering) Yes; Parallel online access possible for up to 10 engineering
systems
Status block Yes; Up to 16 simultaneously (in total across all ES clients)
Single step No
Number of breakpoints 20
Status/control
● Status/control variable
Yes
● Variables
Inputs/outputs, memory bits, DBs, distributed I/Os, timers,
counters
● Number of variables, max.
— of which status variables, max.
200; per job
— of which control variables, max.
200; per job
Forcing
● Forcing, variables
Peripheral inputs/outputs
● Number of variables, max.
200
Diagnostic buffer
● present
Yes
● Number of entries, max.
3200
— of which powerfail-proof
1000
Traces
● Number of configurable Traces
8; Up to 512 KB of data per trace are possible
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED
Yes
● ERROR LED
Yes
6ES7517-3TP00-0AB0 Subject to change without notice
Page 11/
13
09/14/2019 © Copyright Siemens