Data Sheet

Power loss, typ. 1.4W; minimum - typ. specification not possible because load-
dependent
Power loss, max. 5.9W
Interfaces
PROFIBUS PA
● Transmission rate, max.
31.25kbit/s
● Number of connectable PA field devices
6
● Current output to PA field devices, max.
260mA; max. 180 mA total current of all field devices for
operation in the permissible operating voltage range from 16 V to
32 V
● permissible current per spur line
40mA; first spur line 60 mA
Protocols
PROFIBUS DP No
PROFIBUS PA Yes
AS-Interface No
FOUNDATION Fieldbus H1 Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms No
Diagnostics function Yes
Diagnostics indication LED
● Main line status
Yes
● Main line failure
Yes
● Spur line status/fault
Yes
● automatic bus termination
Yes
Potential separation
between main line and spur lines Yes
Isolation
Isolation tested with 2 550 V DC
Degree and class of protection
Degree of protection acc. to EN 60529
● IP66
Yes
Standards, approvals, certificates
Use in hazardous areas
● ATEX Zone 1
Yes
● ATEX Zone 21
Yes
● ATEX Zone 2
Yes
● ATEX Zone 22
Yes
● FM Class I Zone 1
No
● FM Class I Zone 2, Division 2
No
6ES7655-5DX60-1BB0 Subject to change without notice
Page 2/
4
09/13/2019 © Copyright Siemens