User Manual

Getting started with LOGO!
LOGO!
14 Manual, 06/2014, A5E33039675
Which devices are available?
LOGO! Base Modules are available in two voltage classes:
Class 1 ≤ 24 V, i.e. 12 VDC, 24 VDC, 24 VAC
Class 2 > 24 V, i.e. 115 VAC/VDC to 240 VAC/VDC
LOGO! Base Modules are available in two versions:
LOGO! Basic
(version with display): 8 inputs and 4 outputs
LOGO! Pure
(version without display): 8 inputs and 4 outputs
Each module has an expansion interface and an Ethernet interface and provides 44 pre-
configured standard and special function blocks for the creation of your circuit program.
Which expansion modules are available?
LOGO! DM8 digital modules are available for operation with 12 VDC, 24 VAC/VDC and
115 VAC/VDC to 240 VAC/VDC, and are equipped with four inputs and four outputs.
LOGO! DM16 digital modules are available for operation with 24 VDC and 115 VAC/VDC
to 240 VAC/VDC, and are equipped with eight inputs and eight outputs.
LOGO! analog modules are available for operation with 24 VDC and some with 12 VDC,
depending on the specific module. Each is equipped with two analog inputs, two PT100
inputs, two PT100/PT1000 inputs (either PT100 or PT1000 or one of each), or two analog
outputs.
Each digital/analog module has two expansion interfaces for connecting additional modules.
Which display modules are available?
LOGO! Basic
LOGO! TDE
Features of the LOGO! TDE
The LOGO! TDE is available for the 0BA8 series. It provides an additional display that is
wider than the LOGO! Basic. It has four function keys that you can program in your circuit
program as inputs. Like the LOGO! Basic, it has four cursor keys, an ESC key and an Enter
key that you can also program in your circuit program and use for navigation on the
LOGO! TDE.
You can create and download a power-up screen for the LOGO! TDE from LOGO!Soft
Comfort. This screen displays briefly when you initially power on the LOGO! TDE. You can
also upload the power-up screen from the LOGO! TDE to LOGO!Soft Comfort.
The LOGO! TDE provides three main menu commands, respectively for the IP address
selection of a Base Module, the remote settings of the connected Base Module, and the
independent configuration of the LOGO! TDE. The menus for the LOGO! TDE are shown in
Appendix "LOGO! TDE (Page 329)".