User Manual

LOGO! functions
4.4 Special functions list - SF
LOGO!
158 Manual, 06/2014, A5E33039675
Functional description
A 0 to 1 transition at input Trg sets output Q.
If output Q = 0, and input Trg is set hi at least for the duration of T
L
, LOGO! enables the
permanent lighting function and sets output Q accordingly.
LOGO! triggers the off-delay T when input Trg returns to 0 before T
L
has expired.
Output Q is reset when T
a
= T.
You can output an off-warning signal prior to the expiration of the off-delay time (T - T
!
) that
resets Q for the duration of the prewarning time period T
!L
. A subsequent signal at Trg
always resets T and the output Q.
If the block is retentive, LOGO! resets output Q and the expired time to the values before a
power failure; if the block is not retentive, LOGO! resets output Q and the expired time to
defaults after a power failure.
Setting the Par parameter
Note the defaults specified in the topic "Time response (Page 128)".
Note
T, T
!
and T
!L
must all have the same timebase.
View in programming mode (example):
View in parameter assignment mode (example):