User Manual

LOGO! functions
4.4 Special functions list - SF
LOGO!
180 Manual, 06/2014, A5E33039675
4.4.17
Threshold trigger
Short description
The output is set and reset with two configurable threshold triggers.
Symbol in LOGO!
Wiring
Description
Input Fre The function counts the 0 to 1 transitions at input Fre.
1 to 0 transitions are not counted.
Use the following as the input:
inputs I3, I4, I5, I6 for fast counting (only LOGO!
12/24RCE/RCEo and LOGO! 24CE/24CEo): max.
5 kHz, if the fast input is directly connected to the
threshold trigger function block
any other input or circuit component for counting
low frequency signals (typically 4 Hz)
Parameter On: on threshold
Range of values:
0000...9999
Off: off threshold
Range of values:
0000...9999
G_T: time interval or gate time during which the input
pulses are measured
Range of values:
00:00 s...99:99 s
Output Q
Q is set and reset at the thresholds.
Parameter G_T
The gate time G_T can be provided by the actual value of another already-programmed
function. You can use the actual values of the following functions:
Analog comparator (Page 188) (actual value Ax Ay)
Analog threshold trigger (Page 183) (actual value Ax)
Analog amplifier (Page 195) (actual value Ax)
Analog multiplexer (Page 213) (actual value AQ)
Analog ramp (Page 216) (actual value AQ)
Mathematic instruction (Page 227) (actual value AQ)
PI controller (Page 220) (actual value AQ)
Up/down counter (Page 173) (actual value Cnt)
Analog filter (Page 232) (actual value AQ)
Average value (Page 237) (actual value AQ)
Max/Min (Page 234) (actual value AQ)