User Manual

LOGO! functions
4.4 Special functions list - SF
LOGO!
Manual, 06/2014, A5E33039675
221
Parameters SP and Mq
The set-value SP and the value for Mq can be provided by another already-programmed
function. You can use the actual values of the following functions:
Analog comparator (Page 188) (actual value Ax Ay)
Analog threshold trigger (Page 183) (actual value Ax)
Analog amplifier (Page 195) (actual value Ax)
Analog multiplexer (Page 213) (actual value AQ)
Analog ramp (Page 216) (actual value AQ)
Mathematic instruction (Page 227) (actual value AQ)
Up/down counter (Page 173) (actual value Cnt)
Analog filter (Page 232) (actual value AQ)
Average value (Page 237) (actual value AQ)
Max/Min (Page 234) (actual value AQ)
On-delay (Page 136) (current time Ta)
Off-delay (Page 140) (current time Ta)
On-/off-delay (Page 142) (current time Ta)
Retentive on-delay (Page 144) (current time Ta)
Wiping relay (pulse output) (Page 146) (current time Ta)
Edge-triggered wiping relay (Page 148) (current time Ta)
Asynchronous pulse generator (Page 150) (current time Ta)
Stairway lighting switch (Page 154) (current time Ta)
Multiple function switch (Page 156) (current time Ta)
Stopwatch (Page 171) (actual value AQ)
PI controller (actual value AQ)
Threshold trigger (Page 180) (actual value Fre)
Select the required function by the block number. For information on parameter defaults,
refer to the On-delay (Page 136) topic.
Parameters KC, TI
Please note the following circumstances:
If parameter KC has value 0, the "P" function (proportional control) will not be executed.
If parameter TI has value 99:59 m, the "I" function (integral-action control) will not be
executed.
Parameter p (number of decimals)
Applies only to the PV, SP, Min and Max values displayed in a message text.