User Manual

Technical data
A.2 Technical data: LOGO! 230...
LOGO!
Manual, 06/2014, A5E33039675
293
Criterion
Tested in accordance with
Values
Clearance and creepage distance
rating
IEC 60664, IEC 61131-2,
EN 50178
cULus to UL 508, CSA
C22.2 No. 142
Fulfilled
Insulation strength
IEC 61131-2
Fulfilled
Cycle time
Cycle time per function
< 0.1 ms
Startup
Startup time at power-up
Typ. 9 s
S7 communication
Delay time
Max. 100 ms
A.2
Technical data: LOGO! 230...
LOGO! 230RCEo
LOGO! 230RCE
Power supply
Input voltage 115 VAC/VDC to
240 VAC/VDC
115 VAC/VDC to
240 VAC/VDC
Permissible range 85 VAC to 265 VAC
100 VDC to 253 VDC
85 VAC to 265 VAC
100 VDC to 253 VDC
Permissible mains frequency
47 Hz to 63 Hz
47 Hz to 63 Hz
Power consumption
115 VAC
240 VAC
115 VDC
240 VDC
15 mA to 40 mA
15 mA to 25 mA
5 mA to 10 mA
2 mA to 8 mA
15 mA to 40 mA
15 mA to 25 mA
5 mA to 10 mA
2 mA to 8 mA
Voltage failure buffering
115 VAC/VDC
240 VAC/VDC
Typ. 10 ms
Typ. 20 ms
Typ. 10 ms
Typ. 20 ms
Power loss at
115 VAC
240 VAC
115 VDC
240 VDC
1.7 W to 4.6 W
3.6 W to 6.0 W
0.6 W to 1.2 W
0.5 W to 2.0 W
1.7 W to 4.6 W
3.6 W to 6.0 W
0.6 W to 1.2 W
0.5 W to 2.0 W
Backup of the real-time clock at 25
°C
Typ. 20 days Typ. 20 days
Accuracy of the real-time clock
Typ. ± 2 s/day
Typ. ± 2 s/day
Digital inputs
Number
8
8
Electrical isolation
No
No