User Manual

Technical data
A.3 Technical data: LOGO! DM8 230R and LOGO! DM16 230R
LOGO!
Manual, 06/2014, A5E33039675
297
LOGO! DM8 230R
LOGO! DM16 230R
Delay time at 0 to 1:
120 VAC
240 VAC
120 VDC
240 VDC
Delay time at 1 to 0:
120 VAC
240 VAC
120 VDC
240 VDC
Typ. 40 ms
Typ. 30 ms
Typ. 25 ms
Typ. 20 ms
Typ. 45 ms
Typ. 70 ms
Typ. 60 ms
Typ. 75 ms
Typ. 40 ms
Typ. 30 ms
Typ. 25 ms
Typ. 20 ms
Typ. 45 ms
Typ. 70 ms
Typ. 60 ms
Typ. 75 ms
Line length (unshielded)
Max. 100 m
Max. 100 m
Digital outputs
Number
4
8
Output type
Relay outputs
Relay outputs
Electrical isolation
Yes
Yes
In groups of
1
1
Control of a digital input
Yes
Yes
Continuous current I
th
Recommended range of
application ≥ 100 mA at
12 VAC/VDC
Max. 5 A per relay
Recommended range of
application ≥ 100 mA at
12 VAC/VDC
Max. 5 A per relay
Surge current
Max. 30 A
Max. 30 A
Incandescent lamp load (25000
switching cycles) at:
230/240 VAC
115/120 VAC
1000 W
500 W
1000 W
500 W
Fluorescent tubes with ballast
(25000 switching cycles)
10 x 58 W (at 230/240 VAC) 10 x 58 W (at 230/240 VAC)
Fluorescent tubes,
conventionally compensated
(25000 switching cycles)
1 x 58 W (at 230/240 VAC) 1 x 58 W (at 230/240 VAC)
Fluorescent tubes,
uncompensated (25000
switching cycles)
10 x 58 W (at 230/240 VAC) 10 x 58 W (at 230/240 VAC)
Short circuit-proof cos 1
Power protection B16, 600 A
Power protection B16, 600 A
Short circuit-proof cos 0.5 to 0.7
Power protection B16, 900 A
Power protection B16, 900 A
Derating None; across the entire
temperature range
None; across the entire
temperature range
Parallel output circuits for power
increase
Not permitted Not permitted
Protection of output relay (if
desired)
Max. 16 A,
characteristic B16
Max. 16 A,
characteristic B16
Switching rate