User Manual

LOGO! installation and wiring
2.3 Wiring LOGO!
LOGO!
Manual, 06/2014, A5E33039675
39
Circuit protection with DC voltage
To suppress voltage peaks on the power supply lines, install a protection device, for example
DEHN (order number 918 402).
2.3.2
Connecting the LOGO! TDE power supply
You must connect the LOGO! TDE to an external power supply that supplies a voltage of
12 VDC or 24 VAC/VDC. The LOGO! TDE includes a power connector. Connect the power
supply to the power connector then plug the power conncetor to the power supply interface
on LOGO! TDE.
Ethernet interfaces
Power supply
The power connection is non-polar. If you connect a DC power supply to the LOGO!
TDE, you can connect the positive supply wire or negative supply wire to either pin 1
or pin 2.
Pin 3 must be connected to the ground.
Note
Siemens recommends that you protect the LOGO!
TDE with a 0.5 A safety fuse on the
power supply.
2.3.3
Connecting LOGO! inputs
Requirements
At the inputs you connect sensor elements such as: momentary pushbuttons, switches, light
barriers, daylight control switches etc.