Sensor characteristics for LOGO!
LOGO! 12/24RCE
LOGO! 12/24RCEo
LOGO! 24CE
LOGO! 24CEo
LOGO! DM8
12/24R
LOGO! DM8
24
I3 ... I6
I1,I2,I7,I8
I3 ... I6
I1,I2,I7,I8
I1 ... I8
I1 ... I8
Signal status 0
Input current
< 5 VDC
< 0.85 mA
< 5 VDC
< 0.05 mA
< 5 VDC
< 0.85 mA
< 5 VDC
< 0.05 mA
< 5 VDC
< 0.85 mA
< 5 VDC
< 0.85 mA
Signal status 1
Input current
> 8.5 VDC
> 1.5 mA
> 8.5 VDC
> 0.1 mA
> 12 VDC
> 2 mA
> 12 VDC
> 0.15 mA
> 8.5 VDC
> 1.5 mA
> 12 VDC
> 2 mA
LOGO! 24RCE (AC)
LOGO! 24RCEo (AC)
LOGO! DM8 24R (AC)
LOGO! 24RCE (DC)
LOGO! 24RCEo (DC)
LOGO! DM8 24R (DC)
LOGO! 230RCE (AC)
LOGO! 230RCEo (AC)
LOGO! DM8 230R (AC)
LOGO! 230RCE (DC)
LOGO! 230RCEo (DC)
LOGO! DM8 230R (DC)
Signal status 0
Input current
< 5 VAC
< 1.0 mA
< 5 VDC
< 1.0 mA
< 40 VAC
< 0.03 mA
< 30 VDC
< 0.03 mA
Signal status 1
Input current
> 12 VAC
> 2.5 mA
> 12 VDC
> 2.5 mA
> 79 VAC
> 0.08 mA
> 79 VDC
> 0.08 mA
LOGO! DM16 24R
LOGO! DM16 24
LOGO! DM16 230R (AC)
LOGO! DM16 230R (DC)
Signal status 0
Input current
< 5 VDC
< 1.0 mA
< 5 VDC
< 1.0 mA
< 40 VAC
< 0.05 mA
< 30 VDC
< 0.05 mA
Signal status 1
Input current
> 12 VDC
> 2.0 mA
> 12 VDC
> 2.0 mA
> 79 VAC
> 0.08 mA
> 79 VDC
> 0.08 mA
Note
LOGO! 230RCE/230RCEo and expansion module DM16 230R each contains
two groups of
four inputs, for a total of eight. Within
each group, you must operate all inputs on the
same
phase. Different
phases are only possible
between
the groups.
Example: I1 to I4 on phase L1
, I5 to I8 on phase
L2
.
You must not
connect the inputs of the LOGO! DM8 230R to different phases.
Sensor connections
Connecting glow lamps and two-wire proximity switches (Bero) to LOGO! 230RCE/230RCEo
or LOGO! DM8 230R (AC) and LOGO! DM16 230R (AC)
The figure below shows how you connect a switch with a glow lamp to LOGO!. The current
that flows through the glow lamp allows LOGO! to detect a "1" signal even though the switch
contact is not closed. If, however you use a switch that has the glow lamp fitted with a power
supply, this response does not occur.