1. If neither LOGO! nor the inserted card contains a circuit program, the LOGO! Basic
displays the following:
2. LOGO! automatically copies the circuit program on the card to memory and overwrites
the existing circuit program.
3. If there is a circuit program in LOGO! or on the card, LOGO! adopts the operational state
it had prior to power-off. Versions without a display unit (LOGO!...o) automatically change
from STOP to RUN (LED changes from red to green).
4. If you have enabled retentivity for at least one function, or a function is permanently
retentive, LOGO! retains the current values at power-off.
Note
When a power failure occurs while you are entering a circuit program, the program in LOGO!
is missing after power is returned.
Before you modify the circuit program, save a backup copy of your orig
inal to a card or to a
computer using LOGO!Soft Comfort.
2.4.2
Operating states
LOGO! Base Module operating states
LOGO! Base Modules (LOGO! Basic or LOGO! Pure) have two operating states: STOP and
RUN.
STOP
RUN
The display shows that the program is
empty when you start the program
(except for LOGO!...o devices)
Switching LOGO! to programming mode
(except for LOGO!...o devices)
LED is red
(only for LOGO!...o devices)
Display: Screen mask for monitoring I/O and
messages (after START in the main menu) or for
the parameter assignment menu
(except for LOGO!...o devices)
Switching LOGO! to parameter assignment mode
(except for LOGO!...o devices)
LED is green
(only for LOGO!...o devices)