SIMOREG DC Master Product Manual
SIEMENS Energy & Automation 10-25
SIMOREG DC Master Base Drive Panel Operating Instructions
PNU
Description Value range
[Unit]
Steps
No. indices
Factory
setting
Type
See
Change
(Access /
Status)
P131
FDS
(G165)
(G166)
Field current for 55% motor flux (field characteristic, point no. 11)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=40.6
Type: O2
P052 = 3
P051 = 40
Offline
P132
FDS
(G165)
(G166)
Field current for 60% motor flux (field characteristic, point no. 12)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=44.6
Type: O2
P052 = 3
P051 = 40
Offline
P133
FDS
(G165)
(G166)
Field current for 65% motor flux (field characteristic, point no. 13)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=48.9
Type: O2
P052 = 3
P051 = 40
Offline
P134
FDS
(G165)
(G166)
Field current for 70% motor flux (field characteristic, point no. 14)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=53.6
Type: O2
P052 = 3
P051 = 40
Offline
P135
FDS
(G165)
(G166)
Field current for 75% motor flux (field characteristic, point no. 15)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=58.9
Type: O2
P052 = 3
P051 = 40
Offline
P136
FDS
(G165)
(G166)
Field current for 80% motor flux (field characteristic, point no. 16)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=64.9
Type: O2
P052 = 3
P051 = 40
Offline
P137
FDS
(G165)
(G166)
Field current for 85% motor flux (field characteristic, point no. 17)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=71.8
Type: O2
P052 = 3
P051 = 40
Offline
P138
FDS
(G165)
(G166)
Field current for 90% motor flux (field characteristic, point no. 18)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=79.8
Type: O2
P052 = 3
P051 = 40
Offline
P139
FDS
(G165)
(G166)
Field current for 95% motor flux (field characteristic, point no. 19)
0.0 to 100.0
[% of P102]
0.1% of P102
Ind: 4
FS=89.1
Type: O2
P052 = 3
P051 = 40
Offline