Data Sheet

6SL3210-1PE31-1UL0
Data sheet for SINAMICS Power Module PM240-2
MLFB-Ordering data
Figure similar
Rated data
Ambient conditions
General tech. specifications
Input
Output
Ambient temperature
Relative humidity
Number of phases
Max. operation
Storage
Transport
Operation LO
Cooling air requirement
Cooling
Installation altitude
Rated power NEC 480V (HO)
Rated voltage
Number of phases
Line voltage
Line frequency
Rated current (LO)
Rated current (HO)
Rated power IEC 400V (HO)
Power factor λ
Offset factor cos φ
Sound pressure level (1m)
Power loss
Rated current (LO)
Pulse frequency
Rated current (HO)
Max. output current
Output frequency for V/f control
Overload capability
Output frequency for vector control
45.00 kW
60.00 hp
400 V
4 kHz
0.99
71 dB
1.54 kW
110.00 A
90.00 A
180.00 A
94.00 A
104.00 A
0.083 m³/s (2.931 ft³/s)
1000 m (3280.84 ft)
Internal air cooling
1.1 x rated output current (i.e. 110 % overload) for 57 s with a cycle time of 300 s 1.5 × rated output current (i.e. 150 % overload) for 3 s with a cycle time of 300 s
Consignment no. :
Remarks :
Item no. :
Offer no. :
Order no. :
Project :
Client order no. :
1.5 × output current rating (i.e., 150 % overload) for 57 s with a cycle time of 300 s 2 × output current rating (i.e., 200 % overload) for 3 s with a cycle time of 300 s
3 AC
3 AC
380 ... 480 V ±10 %
47 ... 63 Hz
0 ... 200 Hz
0 ... 550 Hz
95 % RH, condensation not permitted
-40 ... 70 °C (-40 ... 158 °F)
-40 ... 70 °C (-40 ... 158 °F)
-20 ... 40 °C (-4 ... 104 °F)
0.95
High Overload (HO)
Low Overload (LO)
Operation HO -20 ... 50 °C (-4 ... 122 °F)
Efficiency η 0.98
55.00 kWRated power IEC 400V (LO)
Rated power NEC 480V (LO) 75.00 hp
Filter class (integrated) -
Technical data are subject to change! There may be discrepancies between calculated and rating plate values.
Generated Mon Sep 16 09:22:36 CEST 2019
Page 1 of 2