The exterior diameter must be between 4 and 6 mm. All wiring must be able to be guided to
the meter through the existing bushings. It may be convenient to connect the cables before
the meter in a single multi-conductor cable on a split box.
Do not connect shielded cables to the side of the meter (connect to one end only).
Pulse module
WZU-P2
Function description
The pulse module WZU-P2 enables the meter to communicate with a pulse collector to
transmit measured values. It outputs pulses that can be derived from the energy, volume,
tariff register 1 or tariff register 2. Two channels are available; their function can be adapted
using the service software.
The outputs are in the form of standard pulses or "fast pulses". The pulse duration is
identical for channel 1 and channel 2.
NOTICE
The module can be plugged into both slots, but fast pulses can only be output via slot 2.
Standard pulses
Standard pulse valences
0.6 2.5 3.5 10 15 25 40 60 150
kWh *)
MJ *)
m
3
1 kWh
10 kWh 100 kWh
1 MJ 10 MJ 100 MJ
0.1 m
3
1 m
3
Nominal flow in m
3
/h
*) depending on the unit for heat energy display
Pulses for energy, volume, and tariff register
Period duration >200 ms
Pulse duration: 100 ms conducting