User Manual

23
Smart Infrastructure
CE2N5324en
2019-06-27
The service software configures and reads out the data via the optical interface.
Data logger
The data logger (optional) permits archiving of data that the user can select from a
predefined set of values. The data logger contains 4 archives to which 8 channels can be
assigned. The data can be assigned to any of the channels. The service software is used for
the configuration.
Archive Time base Storage depth Averaging time for
maximum
Hourly archive 1 hour 45 days 1 hour
Daily archive 1 day 65 days 1 hour
Monthly archive 1 month 15 months 1 hour
Yearly archive 1 year 15 years 1 hour/24 hours
*) For measuring periods of less than 1 hour, the highest value from the maximum values as
calculated within 1 hour applies
The data is recorded with their values and time stamps. The service software configures and
reads out the data via the optical interface.
NOTICE
Data transmission is in a manufacturer-specific format.
Value set for data to be recorded
Meter readings at the end of
the period for...
Energy
Tariff register 1, 2, 3
Volume
Operating time *)
Fault duration *)
Pulse input 1
Pulse input 2
*) Depending on configuration: Hours or days
Instantaneous values at the
end of the period for...
Power
Flow rate
Temperature heat side
Temperature cold side
Temperature difference
Indication of errors
Maximum for... Power
Flow rate
Temperature heat side
Temperature cold side
Temperature difference