User Manual

7
Figure 3
Typical Non-Isolated Installation/Wiring Diagram for ABHW-4B Audible Base
Powered by 24 V Regulated Power Supply
Figure 4
Typical Isolated Installation/Wiring Diagram for ABHW-4B Audible Base
Powered by 24 V Regulated Power Supply
Figure 3 and 4 Notes:
1. RPR-1 remote relay and HTRI or XTRI are used for 24 VDC power supervision. 24 VDC wire
open will cause trouble reported by HTRI. Refer to Installation Instruction of RPR-1 (315-
096055).
2. ABHW-4B terminals 5-6 are polarity insensitive. Line 1 and Line 2 can be either line of device
loop.
3. EOL device of HTRI: 3.6 K, 1/4 W resistor, P/N 140-820185.
EOL device of HTRI: 470 Ohm, 1/4 W resistor, P/N 140-820164.
EOL device of XTRI: 470 Ohm, 1% 1/2 W Resistor, P/N A5Q00073045.
4. ABHW-4B can be wired either Style Z (Class A) or Style Y (Class B).
5. For the max load current, refer to the specifications of the compatible panels listed in this
document.
6. The 24 VDC regulated power supply could be the Aux Power Output from the compatible
panels, or from PAD-3/PAD-4/PAD-5, or other UL listed 24 VDC regulated power supply.
24 V FWR power supply cannot be allowed.