1. When installing FD-UL detectors in a FireFinder XLS
panel, use the following panel versions
· PMI ver 10.02 or later
· Zeus ver 10.02 or later
· DLC ver 06.01 or later
2. Please contact Siemens Canada Limited to obtain
Canadian-specific installation instructions documentation.
3. ABHW-4S alarm current can ONLY be powered from
auxiliary power; device loop power is used for the control
circuits in ABHW-4S.
4. When the audible base ABHW-4S works with FD-UL
series detectors, up to 6 tone patterns and 2 volume levels
can be selected by user with system configuration tool.
5. When the audible base ABHW-4S works with H-series
detector, a fixed 85dB tone is provided and only 2 tones
can be selected (Steady and Temporal 3). Steady: without
a jumper at terminals 3 and 4; Temporal 3: terminals 3
and 4 are shorted with jumper.
6. For additional information on the modules used in an
individual system, refer to the Installation Instructions for
that particular module or contact your authorized Siemens
Industry, Inc. representative.