RHS Alarm contact When short circuit (and not overload) occurs, alarm contact 1NO+1NC changes over which can be used to give
(1NO + 1NC) indication. We need to reset it manually after clearing of short circuit. It performs a function of reclosing lockout.
and/or
Auxiliary Contact This contact can be added to the MPCB with or without built -in 1NO+1NC contact.
(1NO + 1NC)
LHS Shunt Release Shunt trip is used for remotely tripping the MPCB.
or
Undervoltage Release It trips the MPCB on voltage interruption, preventing the undesirable restart of the motor.
On Top Current Limiting For increasing breaking capacity of 3VU13 to 50kA for 8 - 25A
(applicable Module
to 3VU13 only) (independent
mounting)