User Manual

25/101
Building Technologies Operating Instructions for ACS Operating and ACS Service CE1U5640en
HVAC Products 2 Processes Dec. 1, 2005
1. Select the "Plant" menu – Refresh device list:. The program uploads to the PC
all plant data available in the central unit.
2. Check to ensure that all devices are contained on the device list:
A. Check to ensure that the device view is currently in use: "View" menu –
Device view.
B. Start the "Popcard" application via the "Applications" menu – Popcard...
C. In the Popcard window, the Device view to the left shows you the devices
available in the plant:
Check now if you can find all devices and if the device type has been
correctly identified (identifiable by the symbol). Depending on the type of
central unit, the device view is structured in the form of a tree: The nodes
(branches) can be opened or closed by clicking + / -. Only then will be
devices become visible.
D. Devices that have been replaced since the device list was last updated are
identified by the
symbol. You can remove such devices by clicking on
them with the right mouse button and selecting Delete.
Note: The data uploaded contain information about the type of device and the
selected plant diagram. Based on this information, the applications will automatically
show pictures and data points. If you change the plant diagram of a device, you must
transfer the new information to the PC: This takes place via the "Plant" menu –
Refresh reference data points.
When all devices are listed, you can upload and change data of devices and work with
other applications of a plant.
If you wish to make use of more convenient navigation through the plant, refer to
chapter Editing a plant view , where you will find more detailed information.
If not all the devices appear, the missing devices have not been identified by the
central unit, which means that they have not been entered in the central unit’s user
directory. Entry of the devices in the user directory depends on the type of central unit:
OCI700 - LPB, OCI69: These service interfaces have no device list. For this reason,
the ACS… software searches for the existing devices on the bus
OCI700 - KNX: The service interface has no device list. The ACS... software
searches for these devices, depending on the selected search area
OCI600: In the device view, open node Device type central unit, 0 – Segment 0 –
Device: x – Standard – Device directory and enter the name, device number and
segment number in the right half of the window. Note: It may take up to 10 minutes
for the OCI600 to identify the parameterized device
OCI611: To create the device directory, there are 3 choices:
A. Press the LPB button on the OCI611 for 6 seconds to start the device search
run. Note: The search run is completed only when the relevant LED on the
OCI611 stops flashing.
B. In the device view, open node Device type central unit, 0 – Segment 0 –
Device: x – Standard – Device directory and enter the name, the device
number and the segment number in the right half of the window. Then, set data
point Update device data to On. Note: The OCI611 has identified all devices
only when data point Update device data switches automatically back to Off.
C. On the page mentioned under B, you can also start the device search run by
setting data point Create device list to On. Note: The search run is completed
only when the relevant LED on the OCI611 stops flashing.
OZW10: In the device view, open node Device 000 – Standard – Setup M-bus.
Select the Addressing mode on the M-bus and Baud rate on the M-bus you
want to use to search for devices on the M-bus. Set data point Delete device list to
OCI700-LPB, OCI69
OCI700-KNX
OCI600
OCI611
OZW10