3. Enter a free Device address. Both Area and Line cannot be changed. They
will automatically be adopted from the KNX line coupler if such a coupler
exists.
4. The device can be assigned a Device name.
5. Confirm the entry by clicking the Write button.
Automatic addressing:
Automatic address assignment can be made for those devices on the device list that
have an address problem. An address problem exists when a device has no
address yet (device address 255), or when there is an address conflict with some
other device:
1. Highlight the devices with address problem by clicking the address problem
button. Devices with an address problem are highlighted in blue.
2. Select Address assignment - button Automatically. A valid device address will
automatically be assigned to all highlighted devices.
Note: Button Automatically will only be available if at least one device has
been highlighted.
3. When successfully completed, the device list will be updated in the Edit device
list dialog. Check with the help of columns Network address and Status if all
devices have a valid address and the OK status.
Adressing with programming mode:
For Synco devices and KNX line couplers, addresses can be assigned on an
individual basis via addressing mode.
1. Set the required device to addressing mode.
2. Select Address assignment - button Programming mode.... Dialog Address
assignment appears.
3. Different entries are required for Synco devices and KNX line couplers. Button
Programming mode... is available only when exactly one device is in
addressing mode.
Synco devices: Enter a free Device Address. Both Area and Line cannot be
changed.
KNX line couplers: Enter Area and Line. The Device address cannot be
changed.
4. Confirm the entry by clicking the Write button.
OZW10:
On plant with OZW10 M-bus central units, the device list can be edited manually. In
the case of larger plant, the commissioning time can thus be considerably shortened
in comparison with the automatic search run, if only individual devices shall be
added or deleted. In certain cases, radio-based consumption meters from the
Siemeca™ AMR system that shall be connected to the OZW10 M-bus central unit
via the M-bus interface of the WTT16 network node can only be added by using this
function.
To edit the device list, you must first establish a connection to the plant and then
select refresh device list. Then, select the "Plant" menu – Edit device list. The Edit
device list window will appear.
Entering devices:
To add devices to the OZW10 M-bus central unit or the WTT16 network node,
proceed as follows:
1. If you want to add devices to the WTT16 network node, first log on at the
network node. Only devices connected to the M-bus can be added to the
WTT16 network node.
A
utomatic addressing
Programming mode
OZW10
Entering devices