User Manual

69/101
Building Technologies Operating Instructions for ACS Operating and ACS Service CE1U5640en
HVAC Products 3 Applications Dec. 1, 2005
The following files are provided:
messages.his: This file contains the last 500 events the OZW775 central unit has
registered:
• Faults (appearing and disappearing) of the connected devices, of the central unit,
and at the fault inputs of the central unit
• Delivery and attempted delivery of faults and system reports to the message
receivers
• Switching on / off of message suppression
• Switching on / off of setting up mode
Now that the files are listed in the right half of the window, you can copy, or copy and
open files with an editor.
OCI600, OZW10:
After starting the "File transfer" application, the left half of the window provides the
following directories:
• Files on the memory card
• Files directly from the central unit
Make certain you have established a connection to the plant. Use the left mouse button
to click on the directory Files directly from central unit. The right half of the window
shows all files contained in the central unit:
• The directory is automatically uploaded when starting the application if, at that time,
a connection to the central unit exists
• The directory is automatically uploaded if the application has already been started,
in which case a connection to the central unit is established
• You can again upload the directory at any time by using the right mouse button and
clicking on Files directly from central unit and then selecting Upload directory
After the files are listed in the right half of the window, you can copy files, copy files with
the help of an Editor or delete files.
The OCI600 provides the following files:
• REGx.600: In these files, you find the current settings and the last 20 events
of all controllers x = 1…16 that have been defined in the device
directory of the OCI600 central unit
• OCI_LOGx.600: In these files, you find the current settings and the last 20 events
of the logic inputs x = 1…6 of the OCI600 central unit
• OCI_DIGx.600: In these files, you find the current settings and the last 20 events
of the digital inputs x = 1…6 of the OCI600 central unit
If no event has as yet occurred on one of the components, the relevant file does not yet
exist. When the first event occurs, the OCI600 will automatically create a file.
The OZW10 provides the following files:
• OZW_SS1.BIL: This file stores all data that can be displayed on the OZW10. In
particular, the file contains all billing data. Depending on the
parameter settings for the Readout cycle, the OZW10 cyclically
uploads these data and makes them available in that file. The
data in that file are not current since they represent the data of
the last readout cycle.
For more information, refer to the following chapters:
• Files on the memory card
• Formating memory cards
• Copying and opening files
Directly from central unit