User Manual

76/101
Building Technologies Operating Instructions for ACS Operating and ACS Service CE1U5640en
HVAC Products 3 Applications Dec. 1, 2005
selecting a page with the left mouse button, the data points appear in the right half of
the window. The same data point is shown in several columns. The invididual columns
have the following meaning:
Column Description
No.
Consecutive numbering of the data points on a page
Line no.
Referring to the installation instructions of the relevant
device
Address
Address of the device to which the data point belongs
Data pointt
Name of the data point
Value
Value of the data point in the parameter set
Unit
Unit of the data point in the parameter set
Transmission result
Result of transmission:
- OK: Value has successfully been uploaded / downloaded
Selection of data point that shall constitute part of the parameter set
To the left of the data point, there is an entry box. When clicking on such a box, a
tick is added, and when clicking a second time, the tick is removed again. When a
data point is marked, it is selected for downloading or uploading. It constitutes part
of the parameter set
To the left of the pages, there is also an entry box. When clicking on such a box, a
tick is added, and when clicking a second time, the tick is removed again. When a
page is marked, all data points on that page will automatically be marked, or the
marking will be removed again
To the left of the parameter set, there is also an entry box. When clicking on such a
box, a tick is added, and when clicking a second time, the tick is removed again.
When a parameter is marked, all pages and data points of that parmaeter set will
automatically be marked, or the marking will be removed again
Changing the value of the data point in the parameter set
You can change the value of the data point only if you have the required write access,
which depends on your user access. The user level can be changed via the "Tools"
menu – Log on.... Depending on the password the program decides which user level
you are authorized to work on. The user levels correspond to those of the respective
devices: If, in the program, you work on the enduser level, for instance, you can change
the same values as if you were on the enduser level of the respective device.
Only values of user-defined parameter sets can be changed. The data points of
standard parameter sets always retain their default values as supplied.
A. You can change the value of a data point in the parameter set offline (with no
connection to a device).
Select a data point. Press the right mouse button. A menu is opened. From that
menu, select Properties.... Then, window Data point command for that data
point appears. In that window, you can make the appropriate settings.
For this command, you can also double-click on the value or use the following
button:
The change only produces a change of the value in the parameter set. The value
has not yet been downloaded to the device. This takes place only when
downloading the parameter set.
B. To copy the value offline from one data point to another, first use the right mouse
button to click on the data point from which you want to copy the value. Select
Copy. Then, use the right mouse button to click on the data point to which you
want to assign the copied value. Select Paste value.
The values can be copied and added only if the two data points are of the same
type (e.g. both analog values or switching times). The values will then be
transferred to the data points that follow the data point on which Paste value was
executed.
Change the value
Change offline
Copy