Building Technologies CC1N7761en
21.08.2018
Technical data
Mains voltage AC 220 V -15 %...AC 240 V +10 %
AC 100 V -15 %...AC 110 V +10 %
Mains frequency 50...60 Hz ±6 %
Unit fuse, built-in T6.3H250V to DIN EN 60 127
External fuse Max. 10 A (slow)
Power consumption
· During startup
· During operation
8 VA
5 VA
Permissible load on the control outputs
· Per terminal
· Total
Max. 4 A to VDE 0660 AC3
Max. 5 A to VDE 0660 AC3
Degree of protection IP 40 (to be ensured through mounting)
Mounting position Optional
Cable glands · Pg11 or
· BSP ¾“ or
· metric M16 x 1.5
Weight approx. 2 kg
Storage DIN EN 60721-3-1
Climatic conditions Class 1K3
Mechanical conditions Class 1M2
Temperature range -20...+60 °C
Humidity < 95 % r.h.
Transport DIN EN 60 721-3-2
Climatic conditions Class 2K2
Mechanical conditions Class 2M2
Temperature -50...+60 °C
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions Class 3K5
Mechanical conditions Class 3M2
Temperature -20...+60 °C
Humidity < 95 % r.h.
Installation altitude Max. 2,000 m above sea level
Warning!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
· With LAE10
· With LFE10
· With LFE50
General unit data
Environmental
conditions
Flame supervision