User Manual

12/20
Smart Infrastructure CC1N7560en
3/4/2020
Technical data (continued)
Connection cross sections, conductor screw connection
Stranded conductor, fine-wired
(flexible)
Cross section
Min. 0.14 mm²
Max. 1.5 mm²
Stranded conductor, fine-wired
(flexible) with ferrule
Cross section
Min. 0.25 mm²
Max. 1 mm²
Stripping length Approx. 7 mm
Screw tightening torque 0.25 Nm
Note!
AGG9 connector sets!
The AGG9 connectors on the connecting cables for the LMV6 may only be removed or
replaced when the plant is shut down (all-pole disconnection)!
Insertion force / contact
4 N
Withdrawal force / contact
1 N
Tightening torque / screw 0.5 Nm in accordance with
DIN EN 60335-1
Contacting with flat pin connector 6.3 x 0.8 mm in accordance with
DIN EN 46244
Male multipoint connector in accordance
with RAST5 standard
Connection cross sections, conductor screw connection
Stranded conductor Cross section max. 2.5 mm²
Stranded conductor with ferrule Cross section max. 2.5 mm²
Stripping length Approx. 8 mm
Note!
AGG9 connector sets!
The AGG9 connectors on the connecting cables for the LMV6 may only be removed or
replaced when the plant is shut down (all-pole disconnection)!
RAST3.5 connecto
r
Mechanical data
RAST5 connecto
r
Mechanical data