User Manual

9/20
Smart Infrastructure CC1N7560en
3/4/2020
Technical data (continued)
Mains supply: The input current for the power supply is dependent on the operating
status of the LMV6
Rated voltage U
Mains 230 V
Safety shutdown from the operating
position at mains voltage
185 V AC
Restart is initiated when mains
voltage exceeds
195 V AC
Status inputs (with the exception of the safety loop) of the contact feedback network
are used for system supervision and require mains-related input voltage
Safety loop Refer to Terminal loading: Outputs
Contact material recommended for
external signal sources (air pressure
switch, gas pressure switch-min, gas
pressure switch-max, etc.)
Gold-plated silver contacts
Transition / settling behavior /
bounce
- Permissible bounce time of
contacts when switching on/off
Max. 20 ms
(after the bounce time, the contact must
stay closed or open)
Inputs for voltage detection
- ON > 160 V AC
- OFF < 80 V AC
Input currents 0.7 to 1.5 mA peak
Terminal loading: Inputs