User Manual

5/16
Building Technologies Division CC1N7118en
19.05.2016
Life cycle
Burner controls has a designed lifetime* of 250,000 burner startup cycles which, under
normal operating conditions in heating mode, correspond to approx. 10 years of usage
(starting from the production date given on the type field).
This lifetime is based on the endurance tests specified in standard EN 230.
A summary of the conditions has been published by the European
Control
Manufacturers Association
(Afecor) (www.afecor.org).
The designed lifetime is based on use of the burner controls according to the
manufacturer’s Data Sheet. After reaching the designed lifetime in terms of the number
of burner startup cycles, or the respective time of usage, the burner control is to be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
Mechanical design
The oil burner controls are of plug-in design, suitable for installation in any position on
burners, in control cabinets or on control panels.
The housing is made of impact-proof, heat-resistant and flame-retarding plastic.
It is of plug-in design (measuring 91 x 62 x 63 mm, including the plug-in base) and
engages audibly in the plug-in base.
The color of plastic material of burner controls LOA... are executed in black.
The housing includes ...
- the thermoelectric programmer acting on a multi-tilting switching system,
compensated for ambient temperature
- flame signal amplifier with the flame relay
- ... lockout reset button with its integrated lockout indication lamp
If mains voltage drops below about AC 165 V, an electronic circuit ensures that the oil
burner control will prevent burner startup or – without releasing fuel – lockout will be
initiated.
Undervoltage detection