Albatros2 Boiler controllers User manual Edition 2.0 Controller series B CE1U2354en 11. May 2007 RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55..
/156 Siemens Switzerland Ltd. HVAC Products User manual CE1U2354en 11.
Table of contents 1 Summary ......................................................................................................... 9 1.1 Type summary............................................................................................... 10 2 Safety notes................................................................................................... 11 2.1 Product liability ..............................................................................................
Planning .........................................................................................................26 Mounting with base ........................................................................................26 Connection / power supply.............................................................................27 Radio connection ...........................................................................................27 Dimensions and drilling plan ........................................
.2 QAA55... ........................................................................................................ 67 5.2.1 Operation....................................................................................................... 67 Operating elements ....................................................................................... 67 Display choices.............................................................................................. 67 5.2.2 Programming .......................
Primary controller / system pump ..................................................................85 6.11 Boiler..............................................................................................................85 Operating mode .............................................................................................85 Setpoints ........................................................................................................85 Minimum limitation of the return temperature ............
Mixing valve groups basic unit..................................................................... 111 Extension module ........................................................................................ 112 QX extension module .................................................................................. 113 BX extension module................................................................................... 114 H2 extension module.................................................................
Extra functions .............................................................................................139 7.4 Extra functions with AVS75.390...................................................................140 Legend mains voltage..................................................................................142 Legend low-voltage......................................................................................143 8 Technical data.............................................................
1 Summary This User manual describes the products listed in the following table and covers handling and configuration of the controls for readers ranging from endusers to heating engineers. Type reference (ASN) Series Name RVS43.143 RVS63.243 RVS63.283 AVS75.390 AVS37.294 AVS37.390 QAA75.610 QAA75.611 QAA78.610 QAA55.110 AVS16.290 AVS71.390 AVS14.390 AVS13.
1.1 Type summary Wired RF Operation with room unit B B A A Operation with operator unit “basic” D T T (optionally with additional room unit) B E1 D F C B A E1 C 2359Z66 2359Z67 A Operation with operator unit “clear-text” (optionally with additional room unit) B E B A A B C D E E1 F E A Basic unit RVS… Power section AVS16… Room unit QAA75… / 78… Outside sensor AVS13… Operator unit AVS37.294 (clear-text) Operator unit AVS37.
2 Safety notes 2.1 Product liability • The products may only be used in building services plant and applications as described in this document • When using the products, all requirements specified in chapters "Handling" and "Technical data" must be satisfied • The local regulations (for installation, etc.) must be complied with • Do not open the units. If not observed, warranty becomes void. 11/156 Siemens Switzerland Ltd. HVAC Products User manual Safety notes CE1U2354en 11.
3 Mounting and installation 3.1 Regulations Electrical installation • Prior to installing the units, power must be turned off • The connections for mains and low-voltage are separated • For wiring, the requirements of safety class II must be satisfied. Sensor and power cables must not be run in the same cable duct 3.2 Basic units RVS… Planning • Air circulation around the controller must be ensured, allowing the unit to emit the heat produced by it.
Mounting method Screwed On DIN rail A2 2359Z09 A1 B2 2359Z11 B1 A: Mounting / B: Removal Note: To mount the controller on a DIN rail, a mounting clip is required! Dimensions and drilling plan L L1 2358M01 B B1 Dimensions in mm RVS63… RVS43… Total height required 2359Z10 L 280.7 180.7 B 120.7 120.7 H 51.7 51.7 L1 270 170 B1 110 110 Dimension X: Connectors with tongues minimum 70 mm Connector without tongues minimum 60 mm x 13/156 Siemens Switzerland Ltd.
Connection terminals of RVS43.143 N P L L1 4 S3 T2 T1 N L S3 L1 N Q SK2 SK1 R N N S Q2 N Y1 Y2 T N QX1 U Q3 3.2.1 050110A 000020 RVS43.143/109 S050110000020 LPB BSB a X30 b X60 b G+ CLCL+ f X50 h MB DB M B3 k CLCL+ M B9 n CLCL+ M H1 p G+ M B1 n M B2 M BX1 n - M BX2 2354Z08 1PRVS13.143/109 b N L L S3 L1 N P L1 Q 4 S3 T2 T1 N R SK2 SK1 N Q3 S Q2 N Y1 T Y2 N U QX1 N U N U QX3 EX2 FX4 QX4 QX4 Z N Connection terminals of RVS63.243 QX2 3.
Connection terminals of RVS63.283 N L L S3 L1 N L1 P 4 S3 T2 T1 N Q SK2 SK1 h N k Q3 n R N p S Q2 M B3 n N Y1 M B9 n Y2 N M H1 p N Q6 M B1 n N Y5 M BX1 n Y6 M BX2 n N n N M B12 T M B2 U - S M H2 T M BX3 QX2 U M BX4 QX3 U M UX QX4 QX4 FX4 EX2 Z QX1 3.2.3 061107B 000020 RVS63.283/109 S061107000020 LPB BSB MB DB a X30 CLCL+ b X60 CLCL+ b X50 CLCL+ b G+ CLCL+ f G+ 2354Z07 1PRVS63.283/109 b 15/156 Siemens Switzerland Ltd.
Terminal markings Mains voltage Use Space L Live AC 230 V basic unit Protective earth N N Neutral conductor L1 Live AC 230 V burner S3 Output burner fault L1 Live burner Protective earth Neutral conductor Phase 1st burner stage 1st burner stage on Input burner fault Input 1st burner stage hours run Safety loop Safety loop Neutral conductor Protective earth DHW charging pump / diverting valve Neutral conductor Protective earth 1st heating circuit pump 1st heating circuit mixing valve opening Neu
Use Space BSB LPB system X60 X50 X30 Service tool OCI700 Local Process Bus - - Radio module AVS71.390 Extension module AVS75.390 Operator unit / boiler control panel - AVS82.490/109 AVS82.
3.3 Extension module AVS75.390 For planning, mounting location and mounting method, refer to the information given for the basic modules. Dimensions and drilling plan L L1 2358M01 B1 B Dimensions in mm L 108.7 AVS75.390 H 51.7 L1 98 B1 110 The AVS75.390 extension module must be connected to terminal X50 of the basic unit using the AVS83.490/109 connecting cable. The connectors are coded. 3.3.1 Connection terminals of AVS75.390 N N QX21 N T QX22 N QX23 - - - S L L Connections B 120.
Terminal markings Mains voltage L N QX21 N QX22 N QX23 Use Space Live AC 230 V basic unit Protective earth Neutral conductor Assignment according to function Neutral conductor Protective earth Assignment according to function Neutral conductor Protective earth Assignment according to function N L AGP4S.03E/109 T AGP8S.04B/109 S AGP8S.03B/109 Connector type AVS82.491/109 AVS82.
3.4 Operator unit AVS37.294 Mounting method Removal 2358Z32 2358Z30 2358Z31 Installation Connections The AVS37.294 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded. Dimensions 90 96 2358M03 27 17 144 Panel cutout 42.4 (144) 138 +1 0 (96) 2358M05 92 +0.8 0 0.5...3.0 20/156 Siemens Switzerland Ltd. HVAC Products User manual Mounting and installation CE1U2354en 11.
3.5 Operator unit AVS37.390 Connections The AVS37.390 operator unit must be connected to terminal X30 of the basic unit using the AVS82.491/109 connecting cable. The connectors are coded. 2354M01 Dimensions A 0,5 13 A Control panel, front 21/156 Siemens Switzerland Ltd. HVAC Products User manual Mounting and installation CE1U2354en 11.
3.6 Room unit QAA55… Planning @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
3.7 Room unit QAA75… Planning @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
Dimensions and drilling plan 60 2359Z50 185 100 56 4,2 56 100 60 80 82 42 2359Z12 24/156 Siemens Switzerland Ltd. HVAC Products User manual Mounting and installation CE1U2354en 11.
3.8 Wireless components The wireless components should be located such that transmission will be as interference-free as possible. The following criteria must be observed: • Not in the vicinity of electrical cables, strong magnetic fields or equipment like PCs, TV sets, microwave ovens, etc. • Not near larger metal structures or constructional elements with fine metal meshes such as special glass or special concrete • The distance to the transmitter should not exceed 30 meters or 2 floors 3.8.
3.8.2 Room unit QAA78.610 Planning @ The room unit should be located in the main living room while giving consideration to the following points: • The place of installation should be chosen so that the sensor can capture the room temperature as accurately as possible without getting adversely affected by direct solar radiation or other heat or refrigeration sources (about 1.
2359Z61 Mounting without base Connection / power supply The room unit is powered by three 1.5 V Alkali batteries type AA (LR06). Radio connection Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach. Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit.
Example of a display during the test: The digits on the left shows telegrams that have been sent, the digits on the right telegrams that have been received. The test will be ended after 24 telegrams. The test is considered successful when at least 50 % of the telegrams sent have been received. 2359Z140 Operator section Testmode If the test was not successful, some other mounting location is to be selected or the AVS14.390 radio repeater can be used.
3.8.3 • • Wireless outside sensor AVS13.399 The radio transmitter must be installed inside the building. The radio transmitter’s mounting location should be chosen such that batteries can be easily changed. Mounting method Outside sensor 2359Z53 2359Z31 2359Z59 2359Z32 2359Z30 2359Z54 2359Z33 Radio transmitter 2359Z55 AAA AAA Battery Connections Battery transit tab The outside sensor is to be connected to the radio transmitter via a 2-core cable, the connections are interchangeable.
Radio connection 2359Z58 AAA AAA Establishment Make the radio connection in the vicinity of the radio module prior to mounting so that all system are within easy reach. Prerequisite for the radio connection is that all components receive power, which means that the radio module must be correctly connected to the basic unit and the batteries must be correctly installed in the room unit. 1.
3.8.4 Radio repeater AVS14.390 • To establish the radio connection, the device must be provisionally connected to power prior to mounting, enabling the radio connection to be opened and tested. • The radio repeater must be fitted inside the building. Mounting method 2359Z33 2 4 2359Z30 2359Z31 1 Connections Power is supplied via the enclosed power pack. The wires are interchangeable.
3.8.5 Checking the wireless components To check whether the connections to the required system components are operational, consult operating lines 130 through 135 on operating page “Wireless“ (operating level “Commissioning“). 3.9 Power supply AVS16.290 Mounting notes The boiler control panel is designed for installation in floor-standing or wall-hung oil or gas boilers and may only be used for that purpose.
3B 1A 4B 2A 1A 2358A16 S1 H1 3B1 1 1 Si C 2 STB 2 PE L L N N1 L1 S3 1 2 3 4 Mains supply 5 to RVS… basic unit Si Fuse 6.3AT S1 Mains switch with green glow lamp STB = SLT Safety limit thermostat 110°C H1 Signal lamp‚ SLT has cut out 35 Dimensions 48 96 2358M02 96 90 80 (96) 2358M04 92 (96) 92 +0.8 0 0.5...3.0 +0.8 0 33/156 Siemens Switzerland Ltd. HVAC Products User manual Mounting and installation CE1U2354en 11.
4 Prerequisites Commissioning To commission the units, the following working steps must be carried out: • Prerequisite is the correct mounting and correct electrical installation and, in the case of wireless solutions, correctly working radio connections to all required auxiliary units. • Make all plant-specific settings. Special attention must be paid to operating page ”Configuration“.
5 Handling 5.1 QAA75.. / QAA78… / AVS37.. 5.1.
Display choices Heating to Comfort setpoint Info level activated Heating to Reduced setpoint Programming activated Heating to frost protection setpoint Heating temporarily switched off ECO function active Process running – please wait Holiday function active Change battery Reference to heating circuit Burner operating (only oil / gas boiler) Maintenance / special operation Error messages Display of all symbols and segments.
• • • • Heating off Temperature according to frost protection Protective functions active Automatic summer / winter changeover (ECO functions) and automatic 24-hour heating limit active Selecting DHW heating mode The button is used to switch DHW heating mode on and off. The selection made is indicated by a bar which appears below the respective symbol. DHW heating • On The DHW is heated according to the selected switching program. • Off No DHW heating, the protective function is active.
Possible displays Depending on the type of unit, configuration and operating state, some of the info lines listed below may not appear.
Press the info button to switch to info display “Manual mode“, where the setpoint can be adjusted. Chimney sweep function SLT test The chimney sweep function is activated by a short press (maximum 3 seconds) on the chimney sweep button. This function produces the operating state required to make emission measurements (flue gas). The SLT test (SLT = safety limit thermostat) is activated by a long press (longer than 3 seconds) on the chimney sweep button.
5.1.2 Programming Setting principle Settings that cannot be made directly with the operating elements are made in the form of programming. For this purpose, the individual settings are structured in the form of operating pages and operating lines, thus forming practical groups of settings. The following example shows how to set the time of day and the date.
5 The display shows the minutes flashing. Turn the setting knob until the minutes of the time of day are correct. AUTO 2359Z140 Time of day and date Hours / minutes 4 0 8 6 12 16 20 To confirm, press OK. 24 The settings are saved and the displays stops flashing. Now, you can make further settings or you press the operating mode button to return to the basic display. AUTO 2359Z140 Time of day and date Hours / minutes 4 0 8 12 16 20 24 Now, you see the basic display again.
You are now on the required user level. AUTO 0 4 8 12 2359Z140 Time of day and date Text3 section Operator 16 20 24 To reach the OEM level, the relevant code must be entered. Setting structure “Enduser“ The example given here shows that certain user levels do not allow certain settings to be made. The example shows them highlighted. On the unit, they are hidden. Commissioning Heating engineer OEM Enduser Hours / minutes Month / day Year Start of summer time End of summer time Hours Minutes 1...
5.1.4 Min max Unit Function user level Time of day and date E Hours / minutes 1 E Day / month 2 E Year 3 F Start of summertime 5 F End of summertime 6 Operator section E Language 20 Default value The table shows all available settings up to the heating engineer level. However, certain operating lines may be hidden, depending on the type of unit. E = enduser I = commissioning F = heating engineer OL = operating line Legend Operating line Overview of settings 25.03 25.10 00:00 01.01 2004 01.
Unit max Min Default value user level I Function Operating line 135 Operator unit 1 Missing ¦ Ready ¦ No recept’n ¦ Change batt 136 I Operator unit 2 Missing ¦ Ready ¦ No recept’n ¦ Change batt 137 I Operator unit P - - - - No - Mo - Su - Missing ¦ Ready ¦ No recept’n ¦ Change batt 138 I Service unit Missing ¦ Ready ¦ No recept’n ¦ Change batt 140 I Delete all devices No ¦ Yes Time prog heating circuit 1 E Preselection 500 Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦
Default value 24:00 24:00 24:00 24:00 No Unit Function 2nd phase on 2nd phase off 3rd phase on 3rd phase off Default values max user level E E E E E Min Operating line 563 564 565 566 576 00:00 00:00 00:00 00:00 24:00 24:00 24:00 24:00 hh:mm hh:mm hh:mm hh:mm - No ¦ Yes Time program 5 E Preselection 600 Mo - Su - Mo - Su ¦ Mo - Fr ¦ Sa - Su ¦ Mo ¦ Tu ¦ We ¦ Th ¦ Fr ¦ Sa ¦Su 601 602 603 604 605 606 616 1st E E E E E E 1st phase on 1st phase off 2nd phase on 2nd phase off 3rd phase on 3r
Optimum start control max Optimum stop control max Reduced setp increase start Reduced setp increase end Overtemp prot pump circuit 830 832 F F Mixing valve boost Actuator type 833 834 850 F F I Switching differential 2-pos Actuator running time Floor curing function 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Room influence Room temp limitation Boost heating Quick setback -3 − − − / -10 8 8 OL 740 80 20 −−−/1 1 − − − / 0.
Default value 0 0 −−− -15 On Unit Function Optimum start control max Optimum stop control max Reduced setp increase start Reduced setp increase end Overtemp prot pump circuit max user level F F F F F Min Operating line 1090 1091 1100 1101 1120 0 0 − − − / -30 -30 360 360 10 OL 1100 min min °C °C - 5 0 3-position 50 °C - 2 120 Off 20 873 °C s - 95 °C Off ¦ On 1130 1132 F F Mixing valve boost Actuator type 1133 1134 1150 F F F Switching differential 2-pos Actuator running time Floo
Unit Off max Floor curing function Min Default value user level I Function Operating line 1450 - Off ¦ Functional heating ¦ Curing heating ¦ Functional / curing heating¦ Curing/functional heating ¦ Manually 1451 1455 1456 1461 I F F F Floor curing setp manually Floor curing setp current Floor curing day current Excess heat draw 25 0 0 0 0 0 Always 95 95 32 °C °C °C Off ¦ Heating mode ¦ Always 1470 F With buffer storage tank Yes - No ¦ Yes 1172 F With primary controller / system p
Default value On Unit Function H3 Excess heat draw max user level F Min Operating line 2046 8 8 80 80 °C °C Off ¦ On 2048 F Yes H3 with buffer No ¦ Yes 2050 F H2 prim contr/system pump Yes No ¦ Yes Swimming pool 2055 F Setpoint solar heating 2056 F Setpoint source heating 2065 F Charging priority solar 26 22 No No ¦ Yes 2080 F With solar integration Yes No ¦ Yes Primary controller / system pump Primary controller / system pump 2150 I After buffer st tank - Before buffer st
Default value −−− 20 −−− −−− −−− 40 100 None Unit Function Collector start function Min run time collector pump Collector frost protection Collector overtemp prot Evaporation heat carrier Pump speed min Pump speed max Antifreeze max user level F F F F F F F F Min Operating line 3830 3831 3840 3850 3860 3870 3871 3880 −−−/5 5 − − − / -20 − − − / 30 − − − / 60 0 0 60 120 5 350 350 100 100 min s °C °C °C % % 30 200 1 10 100 1500 % l/h 120 40 40 °C °C °C None ¦ Ethylene glycol ¦ ¦ Propylene g
Default value 80 80 Off Unit Function Charging temperature max Recooling temp Recooling heat gen/HCs max user level F F F Min Operating line 5050 5055 5056 8 8 OL 5051 OEM 95 °C °C - Off ¦ On 5057 F Recooling collector Off - Substitute - DHW release - DHW sensor - On - Off ¦ Summer ¦ Always 5060 F Electric immersion heater operating mode Substitute ¦ Summer ¦ Always 5061 F Electric immersion heater release 24h/day ¦ DHW release¦ Time program4/ DHW 5062 F El immersion hea
Default value None Unit Function Relay output QX2 max user level I Min Operating line 5891 - None ¦ Circulating pump Q4 ¦ El imm heater DHW K6 ¦ Collector pump Q5 ¦ H1 pump Q15 ¦ Boiler pump Q1 ¦ Bypass pump Q12 ¦ Alarm output K10 ¦ 2nd pump speed HC1 Q21 ¦ 2nd pump speed HC2 Q22 ¦ 2nd pump speed HCP Q23 ¦ Heating circuit pump HCP Q20 ¦ H pump Q18 ¦ System pump Q14 ¦ Heat en shutoff valve Y4 ¦ Solid fuel boiler pump Q10 ¦Time program 5 K13 ¦ Buffer return valve Y15 ¦ Solar pump ext exch K9 ¦ Sol
Default value None Unit Function Sensor input BX3 max user level I Min Operating line 5932 None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return sensor B7 ¦ DHW circulation sensor B39 ¦ Buffer sensor B4 ¦ Buffer sensor B41 ¦ Flue gas temp sensor B8 ¦ Common flow sensor B10 ¦ Solid fuel boiler sensor B22 ¦ DHW charging sensor B36 ¦ Buffer sensor B42 ¦ Common return sensor B73 ¦ Cascade return sensor B70 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return senso
Unit max Min Default value user level I Function Operating line 6015 Function mixing group 2 Heating circuit 2 ¦ Return temp controller ¦ Prim contr/system pump ¦ DHW primary controller ¦ Instantaneous DHW heater ¦ Return controller cascade 6020 I Function extension module 1 None - None - None ¦ Multifunctional ¦ Heating circuit 2 ¦ Return temp controller ¦ Solar DHW ¦ Prim contr/system pump ¦ DHW primary controller ¦ Instantaneous DHW heater ¦ Return controller cascade 6021 I Function e
Unit max Min Default value Function user level Operating line B4 ¦ Buffer sensor B41 ¦ Flue gas temp sensor B8 ¦ Common flow sensor B10 ¦ Solid fuel boiler sensor B22 ¦ DHW charging sensor B36 ¦ Buffer sensor B42 ¦ Common return sensor B73 ¦ Cascade return sensor B70 ¦ Swimming pool sensor B13 ¦ Collector sensor 2 B61 ¦ Solar flow sensor B63 ¦ Solar return sensor B64 6041 I Sensor input BX22 None None ¦ DHW sensor B31 ¦ Collector sensor B6 ¦ Return sensor B7 ¦ DHW circulation sensor B39 ¦ Buffer
Default value No Unit Function Reset to default parameters max user level F Min Operating line 6205 - No ¦ Yes Check no. heat source 1 6212 I Check no. heat source 2 6213 I Check no. storage tank 6215 I Check no. heating circuits 6217 I 6220 F Software version LPB system Device address 6600 I 6601 F Segment address 6604 F Bus power supply function - 0 0 0 0 0 1 0 0 0 Automatically 199999 199999 199999 199999 99.
Unit −−− 0 −−− 0 −−− 0 −−− 0 Off max - Min Default value Function user level Operating line F History 8 F Error code 8 6816 F History 9 F Error code 9 6818 F History 10 F Error code 10 Maintenance / special operation 7040 F Burner hours interval 7041 F Burner hrs since maintenance 7042 F Burner start interval 7043 F Burn starts since maint 7044 F Maintenance interval 7045 F Time since maintenance 7053 F Flue gas temp limit 7054 F Delay flue gas message 7130 E Chimney sweep function 6814 0 255 -
Default value - Unit Function Contact state H1 max user level I Min Operating line 7841 - Open ¦ Closed 7845 7846 I I Voltage signal H2 Contact state H2 7854 7855 I I Voltage signal H3 Contact state H3 0 - 0 10 °C - 0 - 0 10 Volt Open ¦ Closed Open ¦ Closed 7870 I Burner fault S3 - - 0V ¦ 230V 7881 I 1st burner stage E1 - 0V ¦ 230V 7912 I Input EX2 - 0V ¦ 230V State State of heating circuit 1 8000 I State of heating circuit 2 8001 I State heating circuit P 8002 I
Default value Min max Unit Function user level Operating line Flue gas temp max 8318 I Burner modulation 8326 I 8330 F Hours run 1st stage 8331 F Start counter 1st stage 8332 F Hours run 2nd stage 8333 F Start counter 2nd stage 8505 F Speed collector pump 1 8506 F Speed solar pump ext exch 8507 F Speed solar pump buffer 8508 F Speed solar pump swi pool Collector temp 1 8510 I Collector temp 1 max 8511 I Collector temp 1 min 8512 I dT collector 1/DHW 8513 I dT collector 1/buffer 8514 I dt collector 1/
Default value - Unit Function Heat circ mix valve 2 open max user level I Min Operating line 8761 - - - Off ¦ On 8762 I Heat circ mix valve 2 close Off ¦ On 8765 8770 8771 8773 8774 8795 8800 8801 8803 8820 F I I I I F I I I I Speed heating circuit pump 2 Room temp 2 Room setpoint 2 Flow temperature 2 Flow temp setpoint 2 Speed heating circuit pump B Room temp P Room setpoint P Flow temp setpoint P DHW pump Q3 8825 8826 8830 8831 8832 8835 8836 8850 8851 8852 8853 8900 8901 8930 8931 89
Default value - Unit Function Relay output QX3 max user level I Min Operating line 9033 - - - - - - - - - - - - - Off ¦ On Relay output QX4 9034 Off ¦ On 9050 I Relay output QX21 module 1 Off ¦ On 9051 I Relay output QX22 module 1 Off ¦ On 9052 I Relay output QX23 module 1 Off ¦ On 9053 I Relay output QX21 module 2 Off ¦ On 9054 I Relay output QX22 module 2 Off ¦ On 9055 I Relay output QX23 module 2 Off ¦ On 61/156 Siemens Switzerland Ltd.
5.1.5 AVS37.390Operation Operating elements Select operating mode Show information Chimney sweep function STB test + OK - - ESC 2354Z12 + Ajdust room comfort setpoint Navigation and settings Set DHW nominal setpoint Navigation and settings The above illustration shows an example of the front of an operator unit (not supplied as standard).
Adjusting the room temperature setpoint Press the + / - buttons to increase or decrease the Comfort setpoint . For the Reduced setpoint − Press OK − Select the operating line for the “Reduced setpoint” + OK After each readjustment, wait at least 2 hours, allowing the room temperature to adapt. Adjusting the nominal DHW setpoint Press the + / - buttons to increase or decrease the nominal DHW setpoint. + Displaying information Exception No. 1 No. 2 No. 3 No. 4 No.
3.1.2 Programming Setting principle Settings that cannot be made directly with the operating elements require programming.
The display shows the minutes flashing. Press the "+/-" button until the minutes of the time of day are correct. 4 1 2354Z13 + Press OK to confirm. 5 2354Z13 1 The settings are saved and the displays stops flashing. Now, you can make further settings or You can press the operating mode button to return to the basic display. 2354Z13 1 Now, you see the basic display again. 6 5.1.6 User levels The user levels only allow authorized user groups to make settings.
5.1.
5.2 QAA55... 5.2.1 Operation 2358Z34 Operating elements Select heating mode Adjust room comfort setpoint Navigation and settings Presence button Display choices Burner operating (only oil / gas boiler) Heating to Reduced setpoint Error messages Display of all symbols and segments. 2354Z09 Display Heating to Comfort setpoint 5.2.2 Programming Configuration Settings Used as A long press on the occupancy button enables the service level to be accessed.
6 The settings in detail 6.1 Time of day and date The controller has a yearly clock with time of day, weekday and date. To ensure the controller’s functionality, both the time of day and the date must be correctly set. Summer- / wintertime changeover Line no.
Used as Line no. Operating line 40 Used as Room unit 1 Room unit 2 Room unit P Operator unit 1 Operator unit 2 Operator unit P Service unit This operating line is used to select the use of the operator unit. Depending on use, additional settings will then be required under “Heating circuit assignment“. When using several operator units, it is thus possible to match individual units to specific requirements. • In the case several operator units are used, each application may only be used once.
46 Operation HCP Commonly with HC1 Independently 48 Action occupancy button None Heating circuit 1 Heating circuit 2 Jointly Assignment room unit 1 As room unit 1 (setting 40), the action of the relevant operator unit on heating circuit 1 or on both heating circuits can be assigned. The latter is required especially when using 2 heating circuits and only 1 room unit.
Device list radio Line no.
Standard program Line no. Operating line 516, 536, 556, 576, 616 Default values All time programs can be reset to the default settings. Each time program has its own operating line to make this reset. In that case, individual settings will be lost! 6.5 Holidays HC1 641 642 643 648 Line no.
TRKmax TRK TRR TRF 0 2 4 6 8 10 12 14 16 18 20 22 24 26 °C 2358Z01 TRKmax TRK TRR TRF Comfort setpoint maximum Comfort cooling setpoint Reduced setpoint Frost protection setpoint Frost protection In Protection mode, the room temperature is prevented from falling below a certain level. Thus, the frost protection setpoint of the room temperature is maintained. Comfort setpoint maximum The room temperature can be shifted according to different setpoints.
Heating curve displacement Heating curve adaption Parallel displacement of the heating curve is used to change the flow temperature evenly across the entire outside temperature range or, in other words, if the room temperature is always too high or too low, a readjustment must be made with the help of the parallel displacement. Adaptation of the heating curve is used by the controller to automatically adapt the heating curve to the prevailing conditions.
24-hour heating limit The 24-hour heating limit is used to switch the heating on and off in the course of the day, depending on the outside temperature. This function is used primarily during intermediate seasons (spring and fall) to respond to short-time temperature variations. Example: Setting line e.g.
Setting Type of compensation − − −% 1…99 % Pure weather compensation * Weather compensation with room influence * Pure room compensation 100 % * Outside sensor required. Pure weather compensation The flow temperature is calculated via the heating curve, depending on the composite outside temperature. This type of compensation calls for a correct adjustment of the heating curve since in that case the control gives no consideration to the room temperature.
°C TRx TRw+SDR TRw t 2371D02 ON P OFF TRx TRw SDR P T Actual value of room temperature Room temperature setpoint Room’s switching differential Pump Time Boost heating Line no. HC2 HC1 770 1070 Operating line HCP 1370 Boost heating Boost heating is used to reach the new setpoint more quickly when switching from the Reduced setpoint to the Comfort setpoint, thus reducing the heating up time. During boost heating, the room temperature setpoint is raised by the value set here.
• Function without room sensor: Quick setback switches the heating off for a certain period of time, depending on the outside temperature and the building time constant. Example Duration of quick setback when Comfort setpoint minus Reduced setpoint = 2°C (e.g. Comfort setpoint = 20°C and Reduced setpoint =18°C) Outside temperature composite: 0 2 5 10 15 20 50 15 °C 10 °C 5 °C 0 °C -5 °C -10 °C -15 °C -20 °C 0 0 0 0 0 0 0 0 3.1 1.3 0.9 0.6 0.5 0.4 0.4 0.3 7.7 3.3 2.1 1.6 1.3 1.0 0.9 0.8 15.3 6.
Increase of Reduced setpoint HC1 800 801 Line no. HC2 1100 1101 Operating line HCP 1400 1401 Reduced setp increase start Reduced setp increase end The function is used primarily in connection with heating systems with only little spare capacity (e.g. low-energy houses). In that case, the heating up time would be too long if outside temperatures are low.
Switching differential 2pos For the 2-position actuator, the 2-position switching differential must also be adapted. This is not required when using a 3-position actuator. Mixing valve boost To ensure proper mixing valve flow temperature control, the flow temperature must be higher than the demanded setpoint of the mixing valve flow temperature. The value set here is added to the request. Actuator running time Setting the running time of the actuator used with the mixing valve.
2358Z10 [TVw] 55 50 45 40 35 30 25 20 0 1 7 1 5 X 5 Fh 10 15 18 [Tag] Bh 1 25 Fh + Bh X Fh Bh Start day Functional heating Floor curing heating Excess heat draw HC1 861 Line no. HC2 HC3P Operating line 1161 1461 Excess heat draw Off Heating mode Always Excess heat draw can be triggered by the following functions: − Inputs H1, H2, H3 or EX2 − Storage tank recooling − Solid fuel boiler excess heat draw When dissipation of excess heat is activated, it can be drawn by space heating.
Remote HC1 900 Line no. HC2 1200 Operating line HCP 1500 Optg mode changeover None ¦ Protection ¦ Reduced ¦ Comfort ¦ Automatic In the case of external changeover via inputs H1 / H2 / H3, the operating mode to be used can be selected. 6.7 DHW Setpoints Line no. Operating line 1610 1612 Nominal setpoint Reduced setpoint The DHW can be heated up according to different setpoints.
Legionella function Line no. Operating line 1640 Legionella function Off Periodically Fixed weekday 1641 1642 Legionella funct periodically Legionella funct weekday 1644 1645 1646 1647 Legionella funct time Legionella funct setpoint Legionella funct duration Legionella funct circ pump Monday…Sunday Legionella function • Periodically The legionella function is repeated according to the period of time set (operating line 1641).
6.8 Pump H1/H2/H3 Pump H1/H2/H3 Line no.
• On: Swimming pool heating through solar charging is given priority. This also applies if a storage tank with charging priority (operating line 3822) would have to prefer other heat exchangers. Plant hydraulics Line no. Operating line 2080 With solar integration This setting is made to indicate iff the swimming pool can be charged by solar energy. 6.10 Primary controller / system pump Primary controller / system pump Line no.
In normal operation, maximum limitation of the boiler temperature is the upper limit value of the controlled boiler temperature setpoint and, at the same time, setpoint of the electronic limit thermostat (TR). The setting range of setpoint minimum and setpoint maximum is limited by the setpoint of manual operation. Example when using boiler operating mode “Automatic“: TK °C 80 TK max TKw SDK 70 60 40 2371Z26 50 TKmin Legend TK Boiler temperature TKw Boiler temperature setpoint ...
6.12 Cascade Control Line no. Operating line 3532 3533 Restart lock Switch-on delay Restart lock The restart lock prevents a deactivated heat source from being switched on again. It is released again only after the set time has elapsed. This prevents too frequent switching actions of the heat sources and ensures stable plant operating states. Switch-on delay Correct setting of the switch-on delay ensures that the plant maintains stable operating states.
1st changeover 2nd changeover 3rd changeover 4th changeover P [kW] K1 K2 K3 K3 K4 K1 K2 K2 K3 K4 K1 K1 K2 K3 K4 Lag boiler Lead boiler 2379Z07 K4 100 t P Auto source seq exclusion 200 300 400 t [h] = total number of operating hours of all lead boilers [h] = total output of cascade [kW] Setting automatic source sequence exclusion is only used in connection with the activated heat source sequence (operating line 3540).
6.13 Solar Charging controller (dT) Line no. Operating line 3810 3811 3812 3815 3818 Temp diff on Temp diff off Charg temp min DHW st tank Charging temp min buffer Charging temp min swi pool For charging the storage tank via the heat exchanger, the temperature differential between collector and storage tank / swimming pool must be sufficient, and the collector must have reached the minimum charging temperature for the storage tank / swimming pool .
DHW storage tank During solar charging, preference is given to the DHW storage tank. At every level A, B or C (see below), it is charged with priority. Only then will the other consumers of the same level be charged. As soon as all setpoints of a level are attained, those of the next level are approached, whereby priority is again given to the DHW storage tank. Buffer storage tank During solar charging, preference is given to the buffer storage tank.
Collector start function Min run time collector pump If the temperature at the collector (especially in the case of vacuum tubes) cannot be correctly acquired when the pump is deactivated, the pump can be activated from time to time. The function periodically activates the collector pump for at least the selected minimum running time. Frost protection for the collector Line no.
Speed control Line no. Operating line 3870 3871 Pump speed min Pump speed max Pump speed min The minimum speed for all solar pumps can be selected. Pump speed max The maximum speed for all solar pumps can be selected. Yield measurement Line no. Operating line 3880 3881 3884 Antifreeze Antifreeze concentration Pump capacity The 24-hour and total solar energy yield (operating lines 8526 and 8527) is calculated, based on these data.
Delta T-controller For the boiler pump to be put into operation, a sufficiently great temperature differential between boiler temperature and comparison temperature is required. T TKx SDon 2359Z138 SDoff Bx On QX Off TKx Bx On / Off SDon SDoff t Boiler temperature Actual value of comparison temperature Boiler pump Temp diff on Temp diff off 6.15 Buffer storage tank Automatic locks Line no.
Recooling DHW/HCs • Heating energy can be drawn off either by space heating or the DHW storage tank. This can be selected separately for each heating circuit (operating page heating circuit 1…). Recooling collector • If the collector is cold, the energy can be emitted to the environment via the collector’s surfaces. Plant hydraulics Line no. Operating line 4783 With solar integration Select here whether the buffer storage tank can be charged by solar energy. Return diversion Line no.
Partial charging Line no. Operating line 4800 Partial charging setpoint By hydraulically decoupling the lower buffer storage tank section, the chargeable storage volume is reduced. As a result, the upper storage tank section is charged in a shorter period of time. The lower storage tank section is only charged when charging of the upper section is completed.
6.16 DHW storage tank Charging control Line no. Operating line 5020 5021 5022 Flow setpoint boost Transfer boost Type of charging With B3 With B3 and B31 With B3, legio B3 and B31 Flow setpoint boost The DHW request to the boiler is made up of the current DHW setpoint plus the adjustable charging increase. Increase of transfer boost Heat transfer makes it possible to transport energy from the buffer storage tank to the DHW storage tank.
5062 El immersion heater control External thermostat DHW sensor Electric immersion heater operating mode Substitute The electric immersion heater is only used if the boiler delivers a fault status message or has been shut down via boiler lock. This means that in normal situations the DHW is always heated by the boiler. Summer The electric immersion heater is used as soon as all connected heating circuits have switched to summer operation.
Plant hydraulics Line no. Operating line 5090 5092 5093 With buffer storage tank With prim contr/system pump With solar integration With buffer storage tank If a buffer storage tank is used, it is to be entered here whether the DHW storage tank receives its heat from the buffer storage tank or directly from the boiler. When using alternative heat sources, the buffer storage tank temperature is used as a control criterion for the release of additional heat sources.
6.18 Configuration Heating circuits 1 and 2 HC1 Line no. HC2 5700 5710 Operating line Heating circuit 1, 2 Using this setting, the heating circuits can be switched on and off. DHW sensor B3 Line no. Operating line 5730 DHW sensor B3 Sensors Thermostat Sensors The collector calculates the switching points including the switching differential from the DHW setpoint and the acquired DHW storage tank temperature.
• OFF: The separate circuit is switched off. Every boiler in use can charge the DHW storage tank • ON: The separate circuit is switched on. DHW charging takes place exclusively via the boiler defined for that purpose. For the separate circuit, DHW controlling element Q3 must be set to “Diverting valve”! Boiler Line no.
EX2 FX4 (T6) QX4 (T7) QX4 (T8) Modulating 3-position Modulating UX Use Space Input 1st burner stage hours run Phase 2nd burner stage Z Connector type AGP8S.04C/109 2nd burner stage off 2nd burner stage on Boiler temperature control The functioning and activation and deactivation of the first stage corresponds to that of 2-stage burner operation. Release of modulation is analogous to the release of burner stage 2.
Burner control • 3-position control and modulating UX The actuator is controlled in PID mode. By setting the proportional band (Xp), the integral action time (Tn) and the derivative action time (Tv), the controller can be matched to the type of plant (controlled system). Also, the actuator running time is to be set. • Neutral zone For control operation, a neutral zone is used which is at +/- 1K about the current boiler temperature setpoint.
2 x 1 cascade The 2x1 cascade is a special configuration of the basic unit, where the 2-stage boiler is operated as 2 cascaded 1-stage boilers. Due to the temperature differential between boiler temperature setpoint and boiler temperature sensor B2 (common, mandatory cascade flow temperature sensor), switching on / off of the lag boiler (release and reset integral) takes place according to the control of a 2-stage burner. The same parameters are used.
When using a diverting valve, it is always only one heat exchanger that can be used at a time. Only alternative operation is possible. When using a charging pump, all heat exchangers can be used at the same time. Either parallel or alternative operation is possible. External solar exchanger In the case of solar plants with 2 storage tanks, it must be selected whether the external heat exchanger shall be used jointly for DHW and as a buffer storage tank, or exclusively for one of the two.
Collector pump Q5 When using a solar collector, a circulating pump for the collector circuit is required. Pump H1 Q15 Pump H1 can be used for an additional consumer. Together with an external request for heat at input H1, it is possible to operate an air heater or similar. Boiler pump Q1 The connected pump is used for circulating the boiler water. Bypass pump Q12 The pump connected serves as a boiler bypass pump for maintaining the boiler return temperature.
Heat gen shutoff valve Y4 If the buffer storage tank holds a sufficient amount of heat, the consumers can draw their heat from it, and the heat sources need not be put into operation. Automatic heat generation lock locks the heat sources and hydraulically disconnects them from the rest of the plant with the help of heat source shutoff valve Y4. This means that the heat consumers draw their energy from the buffer storage tank and wrong circulation through the heat sources will be eliminated.
St tank transfer pump Q11 If the temperature level of the buffer storage tank is high enough, the DHW storage tank can be charged by the buffer. This transfer can be made by means of transfer pump Q11. DHW mixing pump Q35 Separate pump for storage tank circulation during the time the legionella function is active. DHW interm circ pump Q33 Charging pump with DHW storage tank using an external heat exchanger. Heat request K27 As soon as there is demand for heat, output K27 is activated.
5960 Function input H3 Optg mode changeover HCs+DHW Optg mode changeover HCs Optg mode changeover HC1 Optg mode changeover HC2 Optg mode changeover HCP Heat generation lock Error/alarm message Min flow temp setpoint Excess heat discharge Release swimming pool Heat request 10V Pressure measurement 10V 5961 Contact type H3 NC NO 5962 5964 5966 Input H1/H3 Min flow temp setpoint H3 Temp value 10V H3 Pressure value 3.
• Central effect (LPB) When using LPB device address = 1, excessive heat dissipation also acts on the consumers connected to the other controllers in the same segment. The distribution of excessive heat from segment 0 across other segments of the system is not possible. Temperature value Heat generation receives heat requests in the form of voltage signals (DC 0...10V). The associated setpoint is to be adjusted on operating line 5954.
T = 130°C T = 110°C T = 90°C T = 70°C T = 50°C S = 5°C [v] 2379Z26 10 8 6 4 2 0 10 20 30 40 50 60 70 80 90 100 110 120 130 [°c] T = maximum value of heat request S = minimum limitation of heat request = 5 °C Pressure value 3.5V H1/H3 The voltage signal present at input H1/H2 is converted to a pressure value in a linear manner. The pressure value at 3.5 V can be adjusted with parameter ”Pressure value 3.5V H1/2”. p Example: D35 = 4bar 4 D35 = 2bar 2 0 p H1 0.5 V 3.
All temperature requests made by the heating circuits and by DHW will be ignored. Frost protection for the boiler will be maintained. The chimney sweep function can be activated although the heat generation lock is switched on. Error/alarm message Input EX2 generates a controller-internal error message. If the “Alarm output” (relay outputs QX2-4, operating lines 5891 – 5894) is appropriately configured, the error message will be forwarded or displayed by an additional contact (e.g.
Primary controller / system pump For this application, the respective settings of operating page “Primary controller / system pump” can be adapted. DHW primary controller For this application, the respective settings of operating page “DHW storage tank” can be adapted. Instantaneous DHW heater For this application, the respective settings of operating page “Instantaneous DHW heater” can be adapted. Return controller cascade For this application, the settings of operating page “Cascade” can be adapted.
Return controller cascade For this application, the respective settings of operating page “Cascade” can be adapted. Connections: Terminal Multifunction Heating circ.2 Return temp controller Solar DHW heating Primary controller DHW primary controller Instantaneous DHW heater Return contr.
BX extension module Can be configured for freely selectable QX…/ BX... Line no.
6071 Signal logic output UX Standard Inverted 6075 Temp value 10V UX Function output UX The voltage-modulated output can be used either for speed-controlled pumps or as an output for a voltage-proportional temperature request. Signal logic output UX The voltage signal can be inverted. Thus, it can also be used to control pumps with variable speeds, or temperature request receivers that use inverted signal logic.
Outside temperature ...-4 °C -5…1.5 °C 1.5 °C... Pump Continuously on ON for 10 minutes at 6-hour intervals Continuously off Graph ON cycle OFF ON takt -6 -5 -4 -3 -2 -1 0 1 2 3 2371Z30 OFF 4 TA °C External requirements Line no.
Plant diagram Line no. Operating line 6212 6213 6215 6217 Check no. heat source 1 Check no. heat source 2 Check no. storage tank Check no. heating circuits To identify the current plant diagram, the basic unit generates a check number. The check number is made up of the lined up part diagram numbers. Structure of control number Every control number consists of 3 columns, each representing the application of a plant component. Every column shows a number with a maximum of 2 digits.
Check no. heat source 1 0 1 3 5 6 8 9 10 11 12 13 14 15 17 18 19 20 22 23 24 25 26 27 No solar 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 * DHW/P x x x DHW +P DHW /P DHW DHW P P x x x x x x x x x x x x x x x x Return temp.
connection Buffer storage tank, heat source valve Buffer storage tank, solar connection, heat source valve 4 5 4 5 13 14 16 17 19 20 22 23 25 26 28 29 Check no.
6.19 LPB system Address / power supply Line no. Operating line 6600 6601 6604 Device address Segment address Bus power supply function Off Automatically 6605 Bus power supply state Off On Device address and segment address The controller’s LPB address is divided into 2 parts each consisting of two 2-digit numerals. Example: 14 Segment number Bus power supply Bus power supply state .
• System: Changeover takes place with all controllers in the entire system (in all segments). The controller must be located in segment 0! Summer changeover The range of action of summer changeover is as follows: • Locally: Local action; the local heating circuit is switched based on operating lines 730, 1030 and 1330.
Outside temperature source • Slave without remote adjustment: The time of day on the controller cannot be readjusted The controller's time of day is constantly and automatically matched to the system time • Slave with remote adjustment: The time of day on the controller can be readjusted; at the same time, the system time is readjusted since the change is adopted from the master.
Burner hours run interval, burner start interval As soon as the selected number of burner operating hours or the selected number of burner starts has elapsed, a service message will be displayed. Counted for the message are the number of operating hours and the number of starts of the first burner stage (input E1). Burner hours run, burner starts since service The current value is summated and displayed. Don this operating line, the value can be reset to 0.
Return mixing valve open / closed Boiler pump Collector pump Collector pump 2 Ext.
6.22 Input / output test Line no. Operating line 7700…7999 The input / output test is used to check the correct functioning of the connected components. When selecting a setting from the relay test, the relevant relay is energized, thus putting the connected component into operation. The correct functioning of the relays and wiring can thus be tested. Important: During the relay test, limitation of the boiler temperature by the electronic control thermostat (TR) remains activated.
Heating mode Reduced Frost protection active Summer operation State of DHW Off Enduser (info level) Limit thermostat has cut out Manual control active Frost protection active Heating mode Reduced Frost protection room active Frost protection flow active Frost protection plant active Summer operation 24-hour Eco active Setback Reduced Setback frost protection Room temp lim Off Commissioning, heating engineer Limit thermostat has cut out Manual control active Frost protection active Recooling via collecto
Charging buffer storage tank In operation for HC, DHW In partial load operation for HC, DHW Released for HC, DHW In operation for DHW In partial load operation for DHW Released for DHW In operation for heating circuit In partial load operation for HC Released for HC Overrun active Released Frost protection active Off State of solar Enduser (info level) Manual control active Fault Frost protection collector active Recooling active Max stor tank temp reached Evaporation protection active Overtemp protection
6.24 Diagnostics of heat source For making diagnostics, the various setpoints, actual values, relay switching states and meter readings can be displayed. Line no. Operating line 8610…8699 6.25 Diagnostics consumers For making diagnostics, the various setpoints, actual values, relay switching states and meter readings can be displayed. Line no. Operating line 8700…9099 128/156 Siemens Switzerland Ltd. HVAC Products User manual The settings in detail CE1U2354en 11.
6.26 List of displays Priorities are assigned to pending errors. From priority 6, alarm messages are delivered, which are used by remote supervision (OCI). In addition, the alarm relay will be set. 6.26.
321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 Instantaneous DHW heater outlet temperature sensor error Upper pressure limit 3 (crossed) Critical lower pressure limit 3 (crossed) BX same sensors BX/extension module same sensors BX/mixing valve group same sensors Extension module same function Mixing valve group same function Extension module / mixing valve group same function Sensor BX1 no function Sensor BX2 no function S
7 Plant diagrams The various applications are shown in the form of basic diagrams and extra functions. The basic diagrams show possible applications that can be implemented without the use of multifunctional outputs. 7.1 Basic diagrams The basic diagrams are examples of plant that can be implemented with standard outputs requiring only a few settings. 7.1.1 Basic diagram RVS43.
7.1.2 Basic diagram RVS63.243 Standard diagram B9 Q3 Y1 B3 Q2 B1 2358A02 RG1 DHW heating with diverting valve B9 Q3 B3 2358A12 RG1 Q2 7.1.3 Basic diagram RVS63.283 Standard diagram B9 Q3 Y5 B3 Q6 Y1 Q2 B12 RG1 2358A03 RG2 B1 132/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
7.2 Versions of heat sources RVS43… RVS63… Modulating 3 position 0…10 V 2354A05 2354A05 2-stage burner 2354A05 1-stage burner RVS63… RVS63… 2354A05 Burner without boiler sensor RVS63… 133/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
7.3 Extra functions in general The extra functions can be selected via operating page “Configuration” and complement the basic diagrams of the respective controllers. The type and number of extra functions that can be applied depend on the multifunctional outputs and inputs QX… or BX… Depending on the type of application, the use of extra functions necessitates a number of appropriate operating line settings.
Solar storage tank and swimming pool charging via diverting valves with 2 collectors B13 Q5 B4 B3 B41 B31 B61 Q16 1 1 0 0 K18 2358A26 B6 K8 Solar storage tank and swimming pool charging via charging pumps with 1 collector B3 B6 Q5 B31 K8 K18 2358Z35 K9 Solar storage tank and swimming pool charging via charging pumps with 2 collectors B13 Q5 B3 B4 B61 Q16 B31 B41 K18 K8 K9 2358A27 B6 135/156 Siemens Switzerland Ltd.
Boiler Boiler pump Bypass pump B2 B2 T2 Q12 2358A07 Q1 Solid fuel boiler pump 2358A08 T2 Return temperature sensor B22 B2 T2 B7 2358A13 2358A22 Q10 Flue gas temperature sensor B2 B8 Q1 2358A23 T2 136/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
Storage tank temperature DHW circulating pump Q3 DHW el imm heater B39 B3 Q3 Q4 B3 Heat source shutoff valve buffer 2358A05 2358A04 K6 2nd DHW sensor Y4 Q3 B3 B4 B31 2358A11 2358A21 B41 Heating circuit Heating circuit pump HCP Q20 2358A10 RG1 137/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
Heat converter 2358A24 System pump Q14 Q14 Swimming pool Swimming pool K18 B6 2358A29 Q5 1 0 K18 Pressureless header Common flow sensor 2358A25 B10 138/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
Extra functions Pump H1/2 2358A09 Q15/18/19 139/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
7.4 Extra functions with AVS75.390 The extra functions can be selected via operating page “Configuration“, operating lines 6020 and 6021, and supplement the basic diagrams of the respective controllers. Mixing heating circuit B9 Y5 Q6 B12 2358A17 RG1/2 This extra function is not possible with 63.283. Return temp controller B2 T8 T2 2358A18 B7 Q1 Y7 Solar DHW heating Q3 B6 B3 Q5 2358A06 B31 Primary controller Y19 B15 2358A19 Q14 140/156 Siemens Switzerland Ltd.
Primary DHW controller Y31 Q3 B35 B3 2358A30 B31 B39 Instantaneous DHW heater B38 Y33 2358A31 Q34 Return controller cascade 2358A32 B10 B70 Q25 Y25 141/156 Siemens Switzerland Ltd. HVAC Products User manual Plant diagrams CE1U2354en 11.
Legend mains voltage Diagram Function Connection T2 Burner 1st stage T1, T2 T8 Burner 2nd stage Release modulating burner QX4 Air damper modulating burner = OPEN Q1 Q2 Q3 Q4 Q5 Q6 Q10 Q12 Q14 Q15/18/19 Q16 Q20 Q25 Q34 Y1 Y4 Y5 Y6 Y7 Y19 Y25 Y26 Y31 Y32 Y33 Y34 K6 K5 K8 K9 K18 Boiler pump 1st heating circuit pump Boiler pump DHW charging pump / diverting valve Circulating pump Collector pump 2nd heating circuit pump Solid fuel boiler pump Bypass pump System pump H1/2/3 pump Collector pump 2 Heating
Legend low-voltage B1 B12 B13 B2 B22 B3 B31 B35 B38 B4 B41 B15 B39 B6 B61 B7 B70 B8 B9 B10 RG1 RG2 Flow temperature sensor HK1 Flow temperature sensor HK2 Swimming pool sensor Boiler temperature sensor TK1 Solid fuel boiler sensor DHW sensor top 2nd DHW sensor bottom DHW flow temperature sensor DHW temperature outlet sensor Buffer storage tank temperature sensor Buffer storage tank temperature sensor Flow sensor primary controller DHW circulation sensor B39 Collector sensor Collector sensor 2 Return tempe
8 Technical data 8.1 Basic units RVS… Power supply Wiring of terminals Functional data Inputs Rated voltage Rated frequency Power consumption Fusing of supply lines Power supply and outputs Software class Mode of operation to EN 60 730 Digital inputs H1 and H2 Analog input H1, H2 Mains voltage S3, 4 and EX2 Outputs AC 230 V (±10%) 50/60 Hz RVS43.143: max. 8.5 VA RVS63.243: max. 10 VA RVS63.283: max. 11 VA max. 10 AT solid wire or stranded wire (twisted or with ferrule): 1 core: 0.5...2.
Interfaces, cable lengths Degree of protection and safety class Standards, safety, EMC, etc. Climatic conditions Weight BSB Max. cable length Basic unit – peripheral device Max. total length Min. cross-sectional area LPB 2-wire connection, not interchangeable 200 m 400 m (max. cable capacitance) 60 nF) 0.5 mm2 (copper cable 1.
Outputs Interfaces Degree of protection and safety class Standards, safety, EMC, etc. Climatic conditions Weight Relay outputs Rated current range Max. switch-on current Max. total current (of all relays) Rated voltage range BSB Max. cable length Basic unit – peripheral device Max. total length Min.
Standards, safety, EMC, etc.
Degree of protection and safety class Standards, safety, EMC, etc.
8.7 Radio repeater AVS14.390 Power supply Nominal voltage Nominal frequency Power consumption Interfaces Radio transmitter Degree of protection and safety class Degree of protection of housing to EN 60 529 Safety class to EN 60 730 Standards, safety, EMC, etc.
8.8 Sensor characteristics 8.8.1 NTC 1 k T [°C] R[Ohm] T [°C] R[Ohm] T [°C] R[Ohm] -30.0 -29.0 -28.0 -27.0 -26.0 -25.0 -24.0 -23.0 -22.0 -21.0 -20.0 -19.0 -18.0 -17.0 -16.0 -15.0 -14.0 -13.0 -12.0 -11.0 -10.0 -9.0 -8.0 -7.0 -6.0 -5.0 -4.0 -3.0 -2.0 -1.0 13’034 12’324 11’657 11’031 10’442 9’889 9’369 8’880 8’420 7’986 7’578 7’193 6’831 6’489 6’166 5’861 5’574 5’303 5’046 4’804 4’574 4’358 4’152 3’958 3’774 3’600 3’435 3’279 3’131 2’990 0.0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 11.0 12.0 13.0 14.
8.8.2 NTC 10 k T [°C] R[Ohm] T [°C] R[Ohm] T [°C] R[Ohm] -30.0 -25.0 -20.0 -15.0 -10.0 -5.0 0.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 175203 129289 96360 72502 55047 42158 32555 25339 19873 15699 12488 10000 8059 6535 5330 4372 50.0 55.0 60.0 65.0 70.0 75.0 80.0 85.0 90.0 95.0 100.0 105.0 110.0 115.0 120.0 125.0 3605 2989 2490 2084 1753 1481 1256 1070 915 786 677 586 508 443 387 339 130.0 135.0 140.0 145.0 150.0 155.0 160.0 165.0 170.0 175.0 180.0 185.0 190.0 195.0 200.
Index 2 2 x 1 cascade ............................................................86 24-hour heating limit..................................................74 2nd pump speed......................................................105 A absolute priority .........................................................82 acknowledgements..................................................122 action changeover functions....................................120 action of operation.............................................
I increase of Reduced setpoint ................................... 79 input / output test .................................................... 125 input test sensor...................................................... 125 L language ................................................................... 68 legionella funct circ pump ............................................................. 83 legionella funct duration ............................................ 83 legionella funct periodically ...........
W weather compensation with room influence ..............76 weekday ....................................................................68 wireless binding................................................................. 70 test mode ............................................................ 70 with buffer storage tank ...................................... 81, 98 with primary controller / system pump ...................... 98 154/156 Siemens Switzerland Ltd.
9 Revision history All changes made to the document since the last issue (see front page) have been registered with the Microsoft Word function "Highlight". To show such text, use the following key combinations: Display: Hide: Ctrl Shift (Num) + Ctrl Shift (Num) - Or select the same functionality with the following menu in Microsoft Word: Menu: [Extras] - [Options] Command: [Highlight] The print file (PDF) does not contain the revision history. 155/156 Siemens Switzerland Ltd.
Siemens Switzerland Ltd Building Technologies Group / HVAC Products Gubelstrasse 22 CH -6301 Zug Tel. +41 41-724 24 24 Fax +41 41-724 35 22 www.sbt.siemens.com © 2007 Siemens Building Technologies Ltd Subject to change 156/156 Siemens Switzerland Ltd. HVAC Products User manual CE1U2354en 11.