ACVATIX™ 6-port control ball valve VWG41.. 6-port control ball valves, PN 16, with externally threaded connection. ● ● ● ● ● ● ● ● ● ● A6V10564480_en--_-G 2020-05-05 Control ball valve body made of hot-pressed brass CW617N DN 10 and DN 20 kvs 0.25...4.25 m3/h Flat sealing, externally threaded connections G..B, per ISO 228-1 Fitting sets ALN..B with external threading per ISO 228-1 Fitting sets ALN..
Use ● ● ● ● ● Used in heated/chilled ceilings as control ball valve. For closed circuit (see Cavitation). Inexpensive: Only one valve with actuator is needed to control a heated and chilled ceiling. Flexible: Various connections can be implemented thanks to external threading. Simple: The brackets, premounted on the actuators, means you can mount them on the ball valves without tools.
Ball characteristic curve DN20 The 6-port control ball valve enables control between two sources through positions 0° and 90°. The 6-port control ball valve is closed at 45°.
Flow diagram DN20 Δpmax = Maximum permissible differential pressure over the ball valve (flow and return), valid for the entire positioning range of the ball valve rotary actuator unit: Δpv100 = Differential pressure over the fully opened ball valve (flow and return) and over the control path at a volume flow V100 V100 = Volume flow through the fully opened ball valve 100 kPa = 1 bar ≈ 10 mWS 1 m3/h = 0.
Type summary Type Order number DN 10 kvs left kvs right [m³/h] [m³/h] 15 Fittings 20 25 0.25 0.4 X - - VWG41.10-0.25-0.4 S55230-V158 VWG41.10-0.25-0.65 S55230-V159 0.25 0.65 X - - VWG41.10-0.25-1.0 S55230-V160 0.25 1 X - - VWG41.10-0.4-0.65 S55230-V161 0.4 0.65 X - - VWG41.10-0.4-1.0 S55230-V162 0.4 1 X - - VWG41.10-0.4-1.3 S55230-V163 0.4 1.3 X - - VWG41.10-0.4-1.6 S55230-V164 0.4 1.6 X - - VWG41.10-0.65-1.0 S55230-V165 0.65 1 X - - VWG41.
Accessories Fittings Type Order no. Description ALN15.152B S55845-Z156 ALN15.202B S55845-Z157 Fittings set made of brass for media temperatures up to 90°C, consisting of ALG13.152B S55845-Z195 ALG15.152B S55845-Z158 ALG15.202B S55845-Z159 ALG15.
Overview of rotary actuators for the 6-port control ball valve Type Order number Torque Operating voltage GDB161.9E S55499-D275 5Nm GDB161.9E/37 S55499-D285 5Nm AC/DC 24 V GDB111.9E/KN S55499-D203 5Nm AC 24 V Positioning Cable length Signal Time [m] DC 0/2...10 V 150 s 0.9 Data sheet 1) A6V10636150 3.7 KNX-TP 0.9 A6V10301232 GDB341.9E S55499-D201 5Nm AC 100...240 V 2-position 0.9 n/a GLB111.9E/MO S55499-D206 10Nm AC 24 V Modbus RTU 0.9 Modbus RTU GSD161.
● Install filter to increase functional security Technical design/mechanical design The Siemens 6-port control ball valve has an internal pressure equalization function that ensures the safe operation of heated and chilled ceilings in a closed valve state (45° position) Changes to media temperature in the heated and chilled ceiling can result in over or under pressure in a closed state and may, under certain circumstances even damage part of the heated and chilled ceiling.
Flow direction Make sure that the valve is mounted in the proper flow direction. Flow direction is indicated on the ball valve body by the symbol on the type label: Commissioning The rotary actuator must be properly mounted before commissioning the 6-port control ball valve. The 6-port control ball valve is delivered in a closed state (middle position). Maintenance The 6-port control ball valve VWG41.. is maintenance free.
Technical data Functional data VWG41.20.. PN class PN 16 Operating pressure 16 bar Maximum differential pressure 2 bar Leakage rate "Air tight" per EN 12266-1, class A Permissible media Chilled water, hot water, water with anti-freeze (max. 50% glycol).
Example: VWG41.20-1.6-2.5 Examples of device combinations Hydraulically balanced solution with 6-port ball valve as changeover and PICV as the control element In this application, the 6-port ball valve changes over between 100% cooling or 100% heating. The PICV valve controls the primary flow for the application.
A6V10564480_Z12 A6V10564480_Z11 The following combinations are possible: DN20: 1. VWG41.20-4.25-4.25 (1” 6-port ball valve) and GDB341.9E (rotary actuator) 2. VPP46.20 (PICV) and SSA61 (0...10 V actuator) DN10: 1. VWG41.10-1.9-1.9 (1/2” 6-port valve) and GDB341.9E (5Nm) / GSD341.9A (2Nm) (rotary actuator) 2. VPP46.15 (PICV) and STA63 (0...10 V actuator) Dimensions Type DN D = Nominal size H = Total height of actuator to wall or ceiling, for mounting, connection, operation, maintenance, etc.
Type Siemens Building Technologies Item NO. Valve type - G G1 Rp ISO 228/1 ISO 228/1 ISO 7-1 [inch] DN C C1 Weight - - [inch] [inch] - [mm] [mm] [kg] ALG15.152B S55845- VWG41.20.. G 1 B Z158 - RP ½ 15 - - 0.183 ALG15.202B S55845- VWG41.20.. G 1 B Z159 - RP ¾ 20 - - 0.299 ALG15.252B S55845- VWG41.20.. G 1 B Z160 - RP 1 25 - - 0,406 ALN15.152B S55845- VWG41.20.. G 1 B Z156 G 1/2 B - 15 28 13 0.208 ALN15.202B S55845- VWG41.20..
Insulation shells H = Total height of actuator with insulation shell to wall or ceiling, for mounting, connection, operation, maintenance etc. Type DN C C1 D D1 E E1 L L1 L2 L3 H Weight [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [mm] [kg] ALI10VWG41 10 78 39 75 37.5 48 27 135 58 55 32 300 0.017 ALI20VWG41 20 85 42.5 80 40 48 48 160 60 60 40 300 0.