User Manual
7
Siemens A6V10564480_en--_-g
Building Technologies 2020-05-05
Overview of rotary actuators for the 6-port control ball valve
Type Order number Torque Operating
voltage
Positioning Cable length Data sheet
1)
Signal Time [m]
GDB161.9E S55499-D275 5Nm AC/DC 24 V DC 0/2...10 V 150 s 0.9 A6V10636150
GDB161.9E/37 S55499-D285 5Nm 3.7
GDB111.9E/KN S55499-D203 5Nm AC 24 V KNX-TP 0.9 A6V10301232
GDB341.9E S55499-D201 5Nm AC 100...240 V 2-position 0.9 n/a
GLB111.9E/MO S55499-D206 10Nm AC 24 V Modbus RTU 0.9 Modbus RTU
GSD161.9A* S55499-D232 2Nm AC/DC 24 V DC 0...10 V 30 s 0.9 n/a
2)
GSD341.9A BPZ:GSD341.9A 2Nm AC 230 V 2-position 30 s 0.9 N4655
1)
Documents can be downloaded at the Internet address, see Section "Product documentation".
2)
GSD161.9A is available as of March 2017
Application examples for the device combinations: See Section Examples for device
combinations
Ordering
Indicate type, order number, order text and number when ordering. Example:
Type Order number Order text Quantity
VWG41.20-0.4-1.3 S55230-V146 6-port control ball valve 1
ALN15.202B S55845-Z157 2x fittings with ISO 228 external threading 3
GDB161.9E GDB161.9E Ball valve actuator, no spring return (NSR) 1
Delivery
6-port control valve (in a closed state), rotary actuator with mounting kits (unassembled),
individually packaged.
Product documentation
Topic Title Document ID
Mounting Mounting instructions 6-port control ball valve VWG41.. A6V10564501
Mounting Mounting instructions rotary actuator G..B.. M4657
Related documents such as environmental declarations, CE declarations, etc., can be
downloaded at the following Internet address:
http://siemens.com/bt/download
Notes
NOTICE
Note the following when servicing a ball valve/rotary actuator:
● Switch off both pump and operating voltage.
● Close shutoff valves.
● Release pressure in the pipes and allow them to cool down completely.
● Disconnect electrical connections from the terminals as needed.
● The rotary actuator must be properly installed prior to recommissioning the ball valve.
● Ensure that there is no cavitation