Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2007 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 1.1 1.2 1.3 About this document ..............................................................................5 Purpose of the document..........................................................................5 Modification index .....................................................................................5 Related documents ...................................................................................5 2 2.1 Introduction ....................................................................
About this document 1 About this document 1.1 Purpose of the document The document describes the differences between the AlgoRex release packages EP7F-Z1 and EP7F-Z2.1. 1.2 Modification index Version 009895_b_en_-009895_b_en_-009895_b_en_-- 1.3 Date 2007-05 2007-05 2007-05 Brief description Chapter 3.2 Chapter 5 Chapter 7 Related documents Reference [1] Document no 6824 Content Operating platform for Tools 5 Building Technologies Fire Safety & Security Products 009895_b_en_--.doc 05.
2 Introduction 2.1 Principal purpose of the project EP7F-Z2.1 AlgoRex EP7F-Z2.1 has been developed in order to fulfil the new extinguishing standard EN12094-1 for single section. 6 Building Technologies Fire Safety & Security Products 009895_b_en_--.doc 05.
Versions and compatibility 3 Versions and compatibility 3.1 AlgoWorks 3.1.1 Program and setup version The AlgoWorks setup version for EP7F-Z2.1 is V1.50. It is a full setup and the program version is 1.50.0-000. Parallel installations with older EP7F AlgoWorks versions are not possible. Therefore, older EP7F AlgoWorks programs must be uninstalled first, before the installation of EP7F-Z2.1 can be started. Please see also documents [1] for further information. 3.1.
Versions and compatibility 3.2 CS1140/45 software 3.2.1 Embedded software version 7.82 There are two different types of embedded SW: – EPROM variants for the older HW types (E3X101, B3Q460/80/85, B3Q560, E3X120, E3H020) The embedded software version for CI1145 (E3X120 board) can be used, but is not compliant with EN12094-1, because of the built in panel type on CI1145.
Versions and compatibility FLASH variants Station type CC1142 CC1143 CI1142 CT1142 CI1143-T1 CI1143-TE CI1143-TL CI1143-T5 CT1143-T1 CT1143-TE CT1143-TL CT1143-T5 CA1142 CA1143-T1 CA1143-TE CA1143-TL CA1143-T5 Name Control unit modular Control unit modular with extended RAM Control unit compact Control terminal Control unit compact (China, simplified) with extended RAM Control unit compact (China, traditional) with extended RAM Control unit compact (Korea) with extended RAM Control unit compact (Thailand)
4 AlgoWorks Software Toolset 4.1 Introduction / overview AlgoWorks EP7F-Z2.1 supports all new functions of the embedded software and the new hardware of EP7F-Z2.1, in particular the new settings for extinguishing functions. 4.2 Site Management 4.2.1 Changed dialogues Default settings The dialogue Default Settings on menu Options has been textual modified. The old entry for EP7F-Z1 is now valid for EP7F-Z2.x as well. The new texts are – Default EP7F-Z1/Z2.x CS1140 – Default EP7F-Z1/Z2.x CS1145 4.2.
AlgoWorks Software Toolset 4.4 Repaired bugs 4.4.1 Wrong gateway listing Bug description Tracking no. FSP00009189 Hotline call none The gateway listing was not correct on structure numbers 1561, 1562 and 1563. An inexistent number was added. Correction / Workaround The inexistent number won’t be added anymore. Bug description Tracking no. FSP00009184 Hotline call none The gateway listing did not show collective elements (1510) correctly if they were used together with zone digital (1610).
Update BDV’s JX_114x_780_04 5 Update BDV’s JX_114x_780_04 5.1 Introduction / overview The major changes compare into BDV JX_1140_780_03 (provided with EP7F-Z2.1) are: - Changed standard texts (see chapter 5.2) 5.2 New standard text TextNr 24084 Modi NEW IMPORTANT INFORMATION Resulting text "Multi verification" As alternative use the older Version JX_114x_780_03 and add the Text see Chapter 5.2 in the file DWR000S.DAT 12 Building Technologies Fire Safety & Security Products 009895_b_en_--.
Embedded software version 7.81 6 Embedded software version 7.81 6.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. The Embedded Software version 781 replaces all other embedded versions, which were published before. Do not mix different embedded software versions at the same customer site.
Embedded software version 7.81 6.2.3 Gateway protocols Bug description Tracking no. FSP00009174 Hotline call none The gateway CK11 did not answer to the command Data Network Acknowledgement Fault (R3886) by sending command Q3846. Correction / Workaround The command Q3846 is now sent. (fixed since CKQ00773) Bug description Tracking no. FSP00009175 Hotline call none The danger management system shows normal condition, even if a detector line was switched off.
Embedded software version 7.81 Bug description Tracking no. FSP00010292 Hotline call none If the connection to danger management system was lost, the buffered output gateway telegrams were not deleted when the connection was connected again. Correction / Workaround Now the output telegrams were deleted, when the connection between gateway and danger management system is established again. 6.2.4 Correct information about blocked event memory Bug description Tracking no.
Embedded Software version 7.82 7 Embedded Software version 7.82 7.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. The Embedded Software version 782 replaces all other embedded versions, which were published before. Do not mix different embedded software versions at the same customer site.
8 Documentation Some documents were updated for EP7F-Z2.1, some are new as well. The current document versions are available as PDF-Files on the Service Technician release CD. The latest versions are always available on the EDMS or STEP.