AlgoRex EP7F-Z2.
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2008 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 1.1 1.2 1.3 About this document ..............................................................................5 Purpose of the document..........................................................................5 Modification index .....................................................................................5 Related documents ...................................................................................5 2 2.1 Introduction ....................................................................
7 7.1 7.2 Embedded Software 7.90......................................................................19 Introduction / overview ............................................................................19 Transponder FDCIO223..........................................................................19 8 8.1 8.2 8.3 Embedded Software 8.00......................................................................20 Introduction / overview .......................................................................
About this document 1 About this document 1.1 Purpose of the document The document describes the differences between the AlgoRex release packages EP7F-Z2.1 and EP7F-Z2.2. It is intended for Tool Coordinators who need to know what is new and/or different in EP7F-Z2.2. 1.2 1.3 Modification index Version A6V10081372_e_en Date 2008-Nov-17 A6V10081372_d_en A6V10081372_c_en 2008-Jun-24 2008-Jun-16 A6V10081372_b_en A6V10081372_a_en 2008-Apr-17 2007-Sep-07 Brief description New chapters 12.2, 12.3, 12.
Versions and compatibility 3 Versions and compatibility 3.1 AlgoWorks 3.1.1 Program and setup version The new AlgoWorks setup version for EP7F-Z2.2 is V1.63.0-000. It is a full setup and the program version is V1.63. Parallel installations with older EP7F AlgoWorks versions are not possible. Therefore, older EP7F AlgoWorks programs must be uninstalled first, before the new installation can be started. Please see also documents [1], [2] and [3] for further information. 3.1.
Versions and compatibility 3.2 Embedded software CS1140/45 3.2.1 Program and setup version The current embedded software setup version for EP7F-Z2.2 is 800. It is a full setup and other embedded software versions may be installed in parallel without problems. Please see document [1], [2] and [3] for further information. 3.2.2 Program / site compatibility The embedded software version 800 is backwards compatible to older versions, but the customer side data has to be converted as well.
Versions and compatibility 3.2.3 Variants of embedded software There are two different variants of embedded SW: EPROM variants for the old HW types (E3X101, B3Q460/480/485, B3Q560, E3X120, E3H020) – FLASH variants for the new HW types (E3X102/103, B3Q660/661/680/685, B3Q565, E3H021) – For checksums of the different versions, please see the detailed documentation which is provided together with the embedded SW on the Tool Coordinator installation CD.
Versions and compatibility 3.3 BDVs J0_114x_800_01 3.3.1 Program and setup version The current BDV setup version for EP7F-Z2.2 is J0_800_01. It is a full setup and other BDV versions can be installed. Please see also documents [1], [2] and [3] for further information. 3.3.2 Program / site compatibility The BDV versions J0_1140_800_01 and J0_1145_800_01 are backwards compatible to older versions, but the customer side data has to be converted.
AlgoWorks Software 1.60 4 AlgoWorks Software 1.60 4.1 Introduction / overview AlgoWorks V1.60 supports all new functions of the embedded software 790 and the BDV versions J0_114x_790_02. 4.2 Tool customizing 4.2.
AlgoWorks Software 1.60 4.4 Station Management 4.4.1 Online help The online help has been adapted a little bit. The following help topics have been changed. Changed New Changed help topics Topic X Welcome to Station Management X Help Release Notes X About Embedded Software Topic file name Description GEN_Welcome_to_Station_Management.HTM GEN_HELP_RELEASE_NOTES.HTM SIM0_Embedded_Software_About.htm New version New version and date New version The flash icons in the compiled help file (*.
AlgoWorks Software 1.60 4.5.2 AlgoWorksTC The online help has been adapted a little bit. The following help topics have been changed. Changed New Changed help topics Topic X AlgoWorksTC functions Topic file name Description -- New version The flash icons in the compiled help file (*.chm) indicate where the changed topics can be found. 4.5.3 Converter The online help has been adapted a little bit. The following help topics have been changed.
AlgoWorks Software 1.62 5 AlgoWorks Software 1.62 5.1 Introduction / overview AlgoWorks V1.62 supports all new functions of the embedded software version 800 and the BDV versions J0_114x_800_01. 5.2 Tool customizing 5.2.
AlgoWorks Software 1.62 5.3 Site Management 5.3.1 Online help The online help has been adapted a little bit. The following help topics have been changed. New Changed Changed help topics X X X Welcome to Site Management X Release Notes X About Embedded Software Export Gateway Data Step 2: Site description dialog X Topic Menu Tools Topic file name Description GEN_Welcome_to_Site_Management.HTM GEN_HELP_RELEASE_NOTES.HTM SIM0_Embedded_Software_About.htm SIM0_Tools_Export_Gateway_Data.
AlgoWorks Software 1.62 5.5 Miscellaneous online helps 5.5.1 AlgoWorksInfo The online help has been adapted a little bit. The following help topics have been changed. Changed New Changed help topics Topic X Welcome to AlgoWorks X Help Release Notes X Related documents Topic file name Description GEN_welcome_to_AlgoWorks.htm GEN_help_release_notes.htm GEN_reference_documents.
AlgoWorks Software 1.62 5.6 Bug fixes / Work arounds Bug description Tracking no. FSP00009047 Hotline call none After a conversion of site data from EP5 to EP7F is carried out, which includes CPU overlapping remote transmission, the converter were not able to convert the data correctly because the necessary structure numbers are different between EP5 and EP7F.
AlgoWorks Software 1.62 Bug description Tracking no. FSP00011910 Hotline call none If an upload command were carried out on a CI1145 station the settings of the I/O types were wrong. Correction The bug has been fixed and the I/O types are correct now. FSP00022071 (FSP00022161) 56408 Hotline call (56123) If a consistency check were carried out on a Dual Core laptop it could happen that the tool was terminating. Tracking no.
AlgoWorks Software 1.63 6 AlgoWorks Software 1.63 6.1 Introduction / overview AlgoWorks V1.63 supports all new functions of the embedded software version 800 and the BDV versions J0_114x_800_01. The changes between the AlgoWorks version 1.62 and 1.63 are only bugfixes. 6.2 Bug fixes / Work arounds Bug description Tracking no. FSP00016411 Hotline call 45317 During creation of controls some references with different criterions can be defined out of a list.
Embedded Software 7.90 7 Embedded Software 7.90 7.1 Introduction / overview Embedded software version 790 supports all new functions of AlgoWorks version V1.60 and the BDV versions J0_114x_790_02. Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site.
Embedded Software 8.00 8 Embedded Software 8.00 8.1 Introduction / overview Embedded software version 800 supports all new functions of AlgoWorks version V1.62 and the BDV versions J0_114x_800_01. Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site.
Embedded Software 8.00 Bug description Tracking no. FSP00018814 Hotline call 56658 After repairing a disconnection between a CT station and its CA, the faulty message disappears correctly but the CA was not working. Correction The error handling between CT-station and CA has been improved. Bug description Tracking no. FSP00022391 Hotline call none If the command 'Reconfig.
BDVs J0_114x_790_02 9 BDVs J0_114x_790_02 9.1 Introduction / overview BDV versions J0_1140_790_02 and J0_1145_790_02 support all new functions of the AlgoWorks V1.60 and embedded software 790. The major changes compare to BDV J0_114x_780_03 (provided with EP7F-Z2.
BDVs J0_114x_790_02 9.3 Changes in ADD file This chapter gives a short overview about the differences in the AlgoWorks Data Definition (ADD) files between J0_114x_780_03.xls and J0_114x_790_02.xls. All changes are documented in detail directly in the ADD files in the additional columns ‘New’, ‘Changed’ and ‘Description’ in each of the sheets. ADD file versions BDV: CS1140 CS1145 File name: J0_1140_790_02.xls J0_1145_790_02.xls Version no. 1.40.00-001 1.40.
Array Indexes EP7F Bitset Labels EP7F Additional Labels EP7F 9.
BDVs J0_114x_790_02 9.6 Changes in BDV online help The BDV online help has been extended to the new functionality. In addition, some corrections have been done in existing help topics. Changed New New or changed help topics Topic X X X X X X X X X X X X X Welcome to Help Release Notes Panel variants and indicators I/O mode coll. line type channel no. Coll.
BDVs J0_114x_800_01 10 BDVs J0_114x_800_01 10.1 Introduction / overview BDV versions J0_1140_800_01 and J0_1145_800_01 support all new functions of the AlgoWorks V1.62 and embedded software 800.
BDVs J0_114x_800_01 10.3 Changes in ADD file This chapter gives a short overview about the differences in the AlgoWorks Data Definition (ADD) files between J0_114x_790_02.xls and J0_114x_800_01.xls. All changes are documented in detail directly in the ADD files in the additional columns ‘New’, ‘Changed’ and ‘Description’ in each of the sheets. ADD file versions BDV: CS1140 CS1145 File name: J0_1140_800_01.xls J0_1145_800_01.xls Version no. 1.50.00-000 1.50.
BDVs J0_114x_800_01 10.4 Changes in Country Defaults This chapter gives a short overview about the differences in Country Defaults between J0_114x_790_02 and J0_114x_800_01. Deleted devices types FDCO221 and FDCIO221 In earlier versions the device types FDCO221 and FDCIO221 were pre defined. Because such devices do not exist and there is no planning to do so, these device types have been deleted. 10.
BDVs J0_114x_800_01 10.7 Bug fixing Bug description Tracking no. FSP00009044 Hotline call none If the connection between C-Bus stations is faulty, the message “No communication to CBus station” appears. Unfortunately the remote transmission is not getting activated. This could be a problem if overlapping remote transmissions is programmed. Correction The corresponding settings have been adapted on all station templates. The infoclass of this message has been changed from 19: Fault 3 to 21: Fault 5.
Miscellaneous 11 Miscellaneous 11.1 Transponder FDCIO223 Restrictions Using special index version The Transponder FDCIO223 may only be used with index 41 or higher. Channels used as sounder lines Sounder tones are not synchronized between different Transponders devices on the same FDnet. However the two sounder lines on the same Transponder are synchronized. Channels used as standard outputs If the channels are defined as I/O’s, some settings about fail safe position can be set.
Update procedures 12 Update procedures For detailed information about the update procedure, please see document [1] and [2]. Back up Please save the data before starting with update procedure. 12.1 Update to AlgoWorks configuration 1.60 12.1.1 File structure The AlgoWorks setup version for EP7F-Z2.2 is V1.60.0-000. It is a full setup and the program version is 1.60. Parallel installations with older EP7F AlgoWorks versions are not possible.
Update procedures 12.1.2 Re-use of excel files The country adapted files MenuCfgData.xls and TextCfgData.xls can be re-used from the old path AW1_5, because no changes have been done. Copy the file from the old folder structure to the new one, to reuse them. Do not forget to adapt the label of version and the correct date on properties tab. Old structure New structure 32 Building Technologies Fire Safety & Security Products A6V10081372_e_en 11.
Update procedures 12.1.3 Re-use of Site and Station Management Online-Help topics New online help projects have been created during the AlgoWorks installation, but the old modified / translated topics can be re-used. Copy your already modified / translated files from the old folder structure AW1_5 to the new structure AW1_6. Do not forget to adapt / translate the new/changed help topics within the new structure. The flash icons in the compiled help file (*.
Update procedures 12.2 Update to AlgoWorks configuration 1.63 (Setup 1.63.0-000) Unfortunately the setup version 1.63.0-000 does not include the necessary AlgoWorks online help source files in the corresponding folders. Therefore the new setup version 1.63.1-000 must be carried out to update the AlgoWorks environment. Please see chapter 12.3, page 35 or chapter 12.4, page 38 for further information. 34 Building Technologies Fire Safety & Security Products A6V10081372_e_en 11.
Update procedures 12.3 Update to AlgoWorks configuration 1.63 (Setup 1.63.1-000) 12.3.1 File structure The AlgoWorks setup version for EP7F-Z2.2 is V1.63.1-000. It is a full setup and the program version is 1.63. Parallel installations with older EP7F AlgoWorks versions are not possible. Therefore, the old EP7F AlgoWorks program version must be uninstalled before. After installation, the folder AW1_6 has been reused.
Update procedures 12.3.2 Re-use of excel files The country adapted files MenuCfgData.xls and TextCfgData.xls can be re-used from an older configuration. Copy the files from the old folder structure to the new one and update them. See chapter 5.2.2 page 13 for environment. Do not forget to adapt the label of version and the correct date on properties tab. Old structure e.g. JX_06_CFG New structure e.g. JX_07_CFG 36 Building Technologies Fire Safety & Security Products A6V10081372_e_en 11.
Update procedures 12.3.3 Re-use of Site and Station Management Online-Help topics New online help projects have been created during the AlgoWorks installation, but the old modified / translated topics can be re-used. Copy your already modified / translated files from the old folder structure to the new structure. Old structure e.g. JX_06_CFG New structure e.g. JX_07_CFG Do not forget to adapt / translate the new/changed help topics within the new structure. The flash icons in the compiled help file (*.
Update procedures 12.4 Update with setup 1.63.1-000 based on setup 1.63.0-000 Unfortunately after carrying out the setup version 1.63.0-000 the AlgoWorks online help topics are not included in the corresponding folders. Therefore the new setup version 1.63.1-000 must be carried out to update the AlgoWorks online help environment. Manually adaptation has to be done as well. 12.4.
Update procedures 12.4.3 Update from setup version 1.63.0-000 to 1.63.1-000 directly If you carry out the new AlgoWorks installation 1.63.1-000 directly, the following information will be shown during the setup sequence. AlgoWorks update info Only the Tool Coordinator structure “…/AW1_6/J0_cfg” will be updated with the online help topics. Earlier created country versions within the folder “AW1_6” have to be updated manually by copying the content into to corresponding folders.
Update procedures 12.5 Update BDV Configuration 12.5.1 Update to xx_114x_790_xx If some minor country modifications have to be done to get a country adapted version, it might be the best to create a new country version, based on international versions J0_1140_790_02 and J0_1145_790_02 and redo the minor changes on the new country version again. If some major country modifications have to be done, the head quarter is able to re-use some parts from a BDV version based on J0_114x_780_03.
Documentation 13 Documentation The following documents have been updated and published on Siemens Intranet.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel. +41 41 – 724 2424 Fax +41 41 – 724 3522 www.siemens.com/buildingtechnologies Document no. A6V10081372_e_en Edition 11.2008 Manual CS11.