AlgoRex EP7F-Z1 Release Notes for Tool Coordinators Building Technologies Control Products and Systems
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2013 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 1.1 1.2 1.3 About this document .............................................................................. 7 Purpose of the document .......................................................................... 7 Modification index ..................................................................................... 7 Related documents ................................................................................... 7 2 2.1 2.2 Introduction ...........................................................
5.4 5.4.1 5.4.2 5.4.3 5.4.4 5.5 5.5.1 5.5.2 5.5.3 5.5.4 5.5.5 5.5.6 5.5.7 5.5.8 Restrictions.............................................................................................. 21 No message ‘Line isolator open’ ............................................................. 21 Button “Alarm devices active” on the CT panel....................................... 21 Australian functionality ............................................................................ 21 No support of Arabic texts ....
13.1 13.1.1 13.1.2 13.2 13.2.1 13.2.2 Restrictions ............................................................................................. 42 LMSmodular SW update for Sinteso....................................................... 42 Default Base Data Variant for EP7F and Rescue Upload ...................... 42 Known bugs ............................................................................................ 43 Alarms from collective line cards acknowledged by DMS ......................
Building Technologies Fire Safety 008322_g_en_-09.
About this document 1 About this document 1.1 Purpose of the document The document describes the differences between the AlgoRex release packages EP7F-SR2 and EP7F-Z1. It is intended for Tool Coordinators who need to know what is new and/or different in EP7F-Z1. 1.2 Modification index Version 008322_g_en_-- 1.
Introduction 2 Introduction 2.1 Principal purpose of the project EP7F-Z1 AlgoRex EP7F-Z1 has been developed in order to introduce the new detection system Sinteso to the AlgoRex fire system family. 2.2 Important rules and information for commissioning IMPORTANT INFORMATION For a smooth commissioning process of Sinteso detection system some rules must be strictly followed. Please read the information in chapter 11 carefully before installing and commissioning an EP7F-Z1 system.
Versions and compatibility 3 Versions and compatibility 3.1 AlgoWorks 3.1.1 Program and setup version The current AlgoWorks setup version for EP7F-Z1 is V1.46.0-000. It is a full setup and the program version is 1.46. Parallel installations with older EP7F AlgoWorks versions are not possible. Therefore, older EP7F AlgoWorks programs must be uninstalled first, before the installation of EP7F-Z1 can be started. Please see also documents [1], [2] and [3] for further information. 3.1.
Versions and compatibility Station type CT1142-T1 CT1142-TE CT1142-TL CT1142-T5 CA1142 CA1142-T1 CA1142-TE CA1142-TL CA1142-T5 Name Control terminal compact (China, simplified) Control terminal compact (China, traditional) Control terminal compact (Korea) Control terminal compact (Thailand) Parallel control console Parallel control console with extended RAM analogous to CT1143 FLASH variants Station type CC1142 CC1143 CI1142 CT1142 CI1143-T1 CI1143-TE CI1143-TL CI1143-T5 CT1143-T1 CT1143-TE CT1143-TL CT11
AlgoWorks Software Toolset 4 AlgoWorks Software Toolset 4.1 Introduction / overview AlgoWorks EP7F-Z1 supports all new functions of the embedded software and the new hardware of EP7F-Z1, in particular the commissioning of the new detection system Sinteso. 4.2 Manually file copy Unfortunately the AlgoWorks setup version V1.46.0-000 installs the file FD20APSConf.bcf into the wrong environment. After carried out the function Refresh AlgoWorks it will be deleted and will be missed for further use.
AlgoWorks Software Toolset 4.3.2 Changes in the AlgoWorks Menu Definition (AMD, MenuCfgData.xls) All changes within the AlgoWorks Menu Definition (AMD) between EP7F-SR2 and EP7F-Z1 are documented in detail directly in the AMD files. Please see the additional columns ‘New’, ‘Changed’ or ‘Description’ in each of the sheets. AMD file version Version no. 1.46.00-000 Date: 2005-05-13 For a detailed list of the changes see the AMD file MenuCfgData.xls.
AlgoWorks Software Toolset 4.4 Site Management 4.4.1 Changed dialogues Default settings The dialogue Default Settings has been modified. The new fields are – Default EP7F-Z1 CS1140 – Default EP7F-Z1 CS1145 They will be set after the first installation of the EP7F-Z1 BDV version and can be modified afterwards, if necessary. Site properties The dialogue has been modified to update the fields Site Name, Description, Customer Name, if necessary. They are editable now. 4.4.
AlgoWorks Software Toolset 4.5 Station Management 4.5.1 New functions Set Loc. Ind. in Conf. Topol. Seq. Order This function is used to set the localisation indexes of the devices on the selected FD20 line in the same order as the configured topology sequence. After this function has been carried out, the service technician is able to finish a localisation with help of the common dialogue box Set loc. Index, Create Element and Link. Set CSX Number in Conf. Topol. Seq.
AlgoWorks Software Toolset 4.5.5 Online help The online help has been adapted and includes the new help topics for Sinteso environment as well. The following help topics have been changed or new created. X Changed New New or changed help topics Topic Topic file name Description X Welcome to the Station Management New version and company name X X Help Release Notes Representation of Commissioning States The Search Function Primary key functions on B3Q6xx GEN_Welcome_to_Station_Management.
Changed AlgoWorks Software Toolset Topic file name Description X Pre-configurted SAM0_Commiss_FD20_setup_preconfig. htm How to commission by pre-configured configuration data. X Device ID number X X Upgrading an existing system Installation order X Device ID number X Move devices How to commission by using device ID number New book created How to upgrade FD20 line by using installation order. How to upgrade FD20 line by using device ID number How to move devices.
AlgoWorks Software Toolset 4.7 Restrictions and known bugs 4.7.1 Disappearances of SIM Short cuts Bug description IPUS no. 5305 After the user has opened the site management all short cuts within the menu bar are shown. When the station management has been opened ones and the user goes back to the site management window the short cuts are not shown anymore. But they are still working. Correction / Workaround Close the site management windows and start AlgoWorks again.
AlgoWorks Software Toolset 4.7.6 Online mode to different station types possible Bug description IPUS no. 5246 It is possible to be online to any station type; it does not matter if the connected station type is compatible to the type, which is opened within the SAM. Correction / Workaround Compare the connected station type with the one you just have opened in AlgoWorks. 4.7.7 Import from SmartHandy Bug description IPUS no.
AlgoWorks Software Toolset 4.7.12 Initial view of “Online mode” Bug description If the user connects to online mode, AlgoWorks does not show the correct node the first time. Correction / Workaround The user should go first online and select the desired node afterwards. IPUS no. 5228 Bug description IPUS no. If a Rescue Upload has been done, no text in the columns “Description” and “Customer Name” will be given. 5267 4.7.
Embedded Software 7.73 5 Embedded Software 7.73 5.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different. After changing a customer site to version 773, the configuration data must downloaded again.
Embedded Software 7.73 5.4 Restrictions 5.4.1 No message ‘Line isolator open’ In case of a short circuit on the FD20 detection line, the two devices next to the short circuit open their line isolators. Normally, this is indicated with a line fault message and an information message ‘Line isolator open’ of the respective devices, i.e. of the logical elements linked with the devices.
Embedded Software 7.73 5.5 Known bugs 5.5.1 Supervision of emergency lines (degrade path) Bug description IPUS no. 5244 If the I-Bus is blocked via switch S4-10 on the E3X101 the signals for the emergency line supervision are also disabled and therefore a fault message 'degrade path fire alarm' is displayed for each station which does not detect the supervision pulses anymore. Correction / Workaround -- 5.5.2 Emergency line 'silence alarm horns' Bug description IPUS no.
Embedded Software 7.73 5.5.6 Pager interface K3I090 Bug description Requested adaptation of K3I090 ESPA protocol: The M2M-terminal seems to have too less memory to accept further messages. In this case the M2M-terminal replies to any message with "2 NAK". This should be handled correctly by K3I090. Correction / Workaround The intervention text is always shown spontaneously, if the field 1348 is active on structure 1390. 5.5.7 IPUS no. 5566 Display of "connecting" text on CT/CI Bug description IPUS no.
Embedded Software 7.74 6 Embedded Software 7.74 6.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different. After changing a customer site to version 774, the configuration data must downloaded again.
Embedded Software 7.74 6.3 Restrictions 6.3.1 No message ‘Line isolator open’ In case of a short circuit on the FD20 detection line, the two devices next to the short circuit open their line isolators. Normally, this is indicated with a line fault message and an information message ‘Line isolator open’ of the respective devices, i.e. of the logical elements linked with the devices.
Embedded Software 7.75 7 Embedded Software 7.75 7.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different. After changing a customer site to version 775, the configuration data must downloaded again.
Embedded Software 7.75 7.3 Restrictions 7.3.1 No message ‘Line isolator open’ In case of a short circuit on the FD20 detection line, the two devices next to the short circuit open their line isolators. Normally, this is indicated with a line fault message and an information message ‘Line isolator open’ of the respective devices, i.e. of the logical elements linked with the devices.
Embedded Software 7.76 8 Embedded Software 7.76 8.1 Introduction / overview Only the Standard embedded software setup is available. The Asia version is not available. 8.2 Repaired bugs Bug description Tracking no.
New BDVs J0_114x_770_03 9 New BDVs J0_114x_770_03 9.1 Introduction / overview EP7F-Z1 includes two new BDV's, which are J0_1140_770_03 and J0_1145_770_03. The major changes compared to BDV J0_114x_730_10 (provided with EP7F-SR1 and EP7F-SR2) are: – – – – Changes in standard texts Changed Country Defaults (FD20 detection system added) New/changed ADD definitions Updated online help The following chapters describe the changes more in detail. 9.2 Tool customizing 9.2.
New BDVs J0_114x_770_03 9.2.2 Changes in the Standard texts This chapter lists the standard text differences of EP7F-Z1 compared to EP7FSR2. new texts: 28 4454 Invalid device(s) on det.
New BDVs J0_114x_770_03 9.2.3 Changes in ADD definitions This chapter gives a short overview of the differences in the AlgoWorks Data Definition (ADD) of EP7F-Z1 compared to EP7F-SR1. All changes are documented in detail directly in the ADD files in the additional columns ‘New’, ‘Changed’ and ‘Description’ in each of the sheets. ADD file versions BDV: CS1140 CS1145 File name: J0_1140_770_03.xls J0_1145_770_03.xls Version no. 1.28.00-000 1.28.
Selection Lists EP7F x x x x x 193 x x x x x x 710 Array Indexes EP7F Bitset Labels EP7F x x x x x x x x x x x x 222 to 225 417 431 442 452 x x 192 x 965 x 1053 1264 1268 1284 1299 x x x x x 1326 x 1314 x 1338 1342 1346 1349 1353 1368 1376 1384 275 277 to 296 58 to 63 93 96 x x x x x x x x x Description: New Field 1419 dbdCfgAPSOrgSetFi New Field 1425 dbdHornAlertSoundFi New Field 1426 dbdHornIntensFi New Field 1427 dbdHornEvacSoundFi x x Deleted Row: 405 412 to 414 415 416 to 41
New BDVs J0_114x_770_03 9.2.4 Changes in Country Defaults This chapter gives a short overview of the differences in the Country Defaults of EP7F-Z1 compared to EP7F-SR2 and EP7F-SR1. Short overview of the changes – FD20 line card, lines and all available FD20 devices added – Combi Create definitions added for automatic detectors, manual call points, DC modules and loop sounders – International defaults set in all new nodes 9.2.
Changed New New BDVs J0_114x_770_03 Topic Topic file name (.htm or .html) Description field 1025 (cmn. CONFIG. ERROR cntr.) does not exist > deleted from table - SE control: Field 1024 (cmn. preALARM cntr.) does not exist > deleted from table - EL RT device: Field 1552 (FAT.FAULT) does not exist > deleted from table - ST CC11, ST Transfer, ST CT11 and ST CK11: Field 1025 (cmn. CONFIG. ERROR cntr.
Changed New New BDVs J0_114x_770_03 Topic Topic file name (.htm or .html) X Emerg. Line mode X Station type FLD0_1229 FLD0_1232 X ST state FLD0_1279 X FU type FLD0_1300 X I-Bus address FLD0_1301 X Loop mode FLD0_1302 X Line no. FLD0_1316 X LED ‘operation’ mode FLD0_1339 X Interv.text after acknowledge X FU state FLD0_1348 X Device type FLD0_1400 X D-bus address FLD0_1410 X Device ID X I/O type FLD0_1412 FLD0_1414 X I/O no.
X X X X X Changed New New BDVs J0_114x_770_03 Topic X X X X X X FLD0_2082 FLD0_2084 New help FLD0_2085 New help FLD0_4422 New topic for BDV 770 and structures 1417, 1418, 1419, 1436 New topic for BDV 770 and structures 1417, 1418, 1419, 1436 Information for sales release added FLD0_1534 X AI’s on acknowledge FLD0_1602 X TEST timeout [min.] X RT device existing X Overwrite protection [h] CONFIG.
Supported devices / non-supported features 10 Supported devices / non-supported features 10.1 Supported devices AlgoRex EP7F-Z1 (Embedded SW and AlgoWorks) supports more Sinteso device types than are available at the time of the release. Following devices are supported and available: S-LINE C-LINE Automatic Detectors Comment Sub-types (-8, -9 etc.
Supported devices / non-supported features 10.2 Non-supported features Some features of the new Sinteso devices are not supported with EP7F-Z1. The following table gives an overview: Device type FDCI222 FDCIO221 FDCIO222 Feature supervision of inputs (minimum time an input must be active before it is evaluated). FDCIO221 FDCO221 FDCIO222 Pulse output (single pulse with configurable length). FDCIO221 FDCIO222 Supervision of confirmation input directly in the device.
Important information about Sinteso commissioning 11 Important information about Sinteso commissioning 11.1 General This chapter informs about important rules and best practice concerning commissioning of Sinteso detection lines. Please read the information carefully and follow the rules before installing and commissioning a customer site. Otherwise different problems might occur during commissioning. 11.2 Commissioning rules The following rules are mandatory for commissioning an FD20 line correctly.
Important information about Sinteso commissioning 11.3 Best practice The following workflow / manipulations are helpful and recommended: Suggestion It is recommended to exchange detectors one by one. If you do not change detectors one by one a Re-configure D-Bus command might be necessary after changing. Reason / Comment Each manipulation on the line must be properly registered by the system before the next one can be processed.
Important information about Sinteso commissioning 11.4 Restrictions and known bugs Please note the following restrictions and known bugs of EP7F-Z1. Restriction / bug / symptom The message 'Localization by TOPOLOGY read-in' does not disappear after termination of the Device Readin command. A short-circuit on a Sinteso detection line can lead to incorrect fault messages of devices on the line. These messages appear in addition to the messages indicating the line fault.
Update procedure EP7F-SR2 to EP7F-Z1 12 Update procedure EP7F-SR2 to EP7F-Z1 For detailed information about the update procedure from EP7F-SR2 to EP7F-Z1, please see document [2]. 13 Miscellaneous 13.1 Restrictions 13.1.1 LMSmodular SW update for Sinteso The LMSmodular software will be updated soon to support Sinteso devices as well. Please contact the corresponding Product Manager for LMSmodular. 13.1.
Miscellaneous 13.2 Known bugs These known bugs are not EP7F-Z1 independent. 13.2.1 Alarms from collective line cards acknowledged by DMS Bug description IPUS no. 5280 If the AlgoRex system is connected to a danger management system (DMS), alarms from the collective lines must be acknowledged twice by the DMS. Correction / Workaround -- 13.2.2 CBA line card Bug description IPUS no. 5317 If the AlgoRex system includes a CBA-Card (E3M120) the system generates sometimes a FATAL FAULT message.