AlgoRex EP7F-Z1 Release Notes for Sevice Technicans Building Technologies Control Products and Systems
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2013 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 1.1 1.2 1.3 About this document .............................................................................. 5 Purpose of the document .......................................................................... 5 Modification index ..................................................................................... 5 Related documents ................................................................................... 5 2 2.1 2.2 Introduction ...........................................................
Building Technologies Fire Safety 009158_c_en_-09.
About this document 1 About this document 1.1 Purpose of the document The document describes the differences between the AlgoRex release packages EP7F-SR2 and EP7F-Z1. 1.2 Modification index Version 009158_c_en_-- 1.3 Date Sep-2013 Brief description Information about Embedded SW 776 Related documents Reference [1] Document no 6824 Content Operating platform for Tools 5 Building Technologies Fire Safety 009158_c_en_-09.
Introduction 2 Introduction 2.1 Principal purpose of the project EP7F-Z1 AlgoRex EP7F-Z1 has been developed in order to introduce the new detection system Sinteso to the AlgoRex fire system family. 2.2 Important rules and information for commissioning IMPORTANT INFORMATION For a smooth commissioning process of Sinteso detection system some rules must be strictly followed. Please read the information in chapter 10 carefully before installing and commissioning an EP7F-Z1 system.
Versions and compatibility 3 Versions and compatibility 3.1 AlgoWorks 3.1.1 Program and setup version The current AlgoWorks setup version for EP7F-Z1 is V1.46.0-000. It is a full setup and the program version is 1.46. Parallel installations with older EP7F AlgoWorks versions are not possible. Therefore, older EP7F AlgoWorks programs must be uninstalled first, before the installation of EP7F-Z1 can be started. Please see also document [1] for further information. 3.1.
Versions and compatibility Station type CA1142 CA1142-T1 CA1142-TE CA1142-TL CA1142-T5 Name Parallel control console Parallel control console with extended RAM analogous to CT1143 FLASH variants Station type CC1142 CC1143 CI1142 CT1142 CI1143-T1 CI1143-TE CI1143-TL CI1143-T5 CT1143-T1 CT1143-TE CT1143-TL CT1143-T5 CA1142 CA1143-T1 CA1143-TE CA1143-TL CA1143-T5 Name Control unit modular Control unit modular with extended RAM Control unit compact Control terminal Control unit compact (China, simplified) wi
Algoworks Software Toolset 4 Algoworks Software Toolset 4.1 Introduction / overview AlgoWorks EP7F-Z1 supports all new functions of the embedded software and the new hardware of EP7F-Z1, in particular the commissioning of the new detection system Sinteso. 4.2 Site Management 4.2.1 Changed dialogues Default settings The dialogue Default Settings has been modified.
Algoworks Software Toolset 4.3 Station Management 4.3.1 New functions Set Loc. Ind. in Conf. Topol. Seq. Order This function is used to set the localisation indexes of the devices on the selected FD20 line in the same order as the configured topology sequence. After this function has been carried out, the service technician is able to finish a localisation with help of the common dialogue box Set loc. Index, Create Element and Link. Set CSX Number in Conf. Topol. Seq.
Algoworks Software Toolset 4.4 Repaired bugs 4.4.1 Information about “Time stamps” within AlgoWorks Bug description IPUS no. -The version keys (time stamps) were not visible on AlgoWorks only on the panel by using the soft key “Poll information”. Correction The version key are visible in AlgoWorks on tab “Service” on the corresponding station node. The names are CONFIG. DATA version key, CUSTOMERTEXT version key and STANDARD TEXT version key.
Embedded software version 7.73 5 Embedded software version 7.73 5.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different.
Embedded software version 7.74 6 Embedded software version 7.74 6.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different.
Embedded Software version 7.75 7 Embedded Software version 7.75 7.1 Introduction / overview Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. Do not mix different embedded software versions at the same customer site. Except the gateway version, it could be different.
Embedded Software version 7.76 8 Embedded Software version 7.76 8.1 Introduction / overview Only the Standard embedded software setup is available. The Asia version is not available. 8.2 Repaired bugs Bug description Tracking no.
Supported devices 9 Supported devices AlgoRex EP7F-Z1 (Embedded SW and AlgoWorks) supports more Sinteso device types than are available at the time of the release. Following devices are supported and available: S-LINE C-LINE Automatic Detectors Comment Sub-types (-8, -9 etc.
Important information about Sinteso commissioning 10 Important information about Sinteso commissioning 10.1 General This chapter informs about important rules and best practice concerning commissioning of Sinteso detection lines. Please read the information carefully and follow the rules before installing and commissioning a customer site. Otherwise different problems might occur during commissioning. 10.2 Commissioning rules The following rules are mandatory for commissioning an FD20 line correctly.
Important information about Sinteso commissioning 10.3 Best practice The following workflow / manipulations are helpful and recommended: Suggestion It is recommended to exchange detectors one by one. If you do not change detectors one by one a Re-configure D-Bus command might be necessary after changing. Reason / Comment Each manipulation on the line must be properly registered by the system before the next one can be processed.
Documentation 11 Documentation Most documents were changed/updated for EP7F-Z1. They are now available as DOC-Files (Microsoft Word format) as well. The documents are available as PDFFiles on the Tool Coordinator release CD. The latest version is always available on the EDMS or STEP.
Siemens Switzerland Ltd Infrastructure & Cities Sector Building Technologies Division International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 – 724 24 24 www.siemens.com/buildingtechnologies Document no. 009158_c_en_-- Edition 09.