AlgoRex EP7F-Z2.
Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2008 Copyright by Siemens Switzerland Ltd Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor.
1 1.1 1.2 1.3 About this document ..............................................................................5 Purpose of the document..........................................................................5 Modification index .....................................................................................5 Related documents ...................................................................................5 2 2.1 Introduction ....................................................................
9 9.1 9.2 9.3 9.4 9.5 9.6 BDVs JX_114x_800_01 .........................................................................19 Introduction / overview ............................................................................19 Changes in standard texts file.................................................................19 Changes in Country Defaults ..................................................................20 Changes in Station Templates ..............................................................
About this document 1 About this document 1.1 Purpose of the document The document describes the differences between the AlgoRex release packages EP7F-Z2.1 and EP7F-Z2.2 1.2 Modification index Version A6V10081374_b_en A6V10081374_a_en 1.
Introduction 2 Introduction 2.1 Principal purpose of the EP7F-Z2.2 The release package AlgoRex EP7F-Z2.2 has been developed in order to expand the range of Sinteso device types on the AlgoRex fire system such as the Transponder (FDCIO223). Additionally some modification has been done to fulfil the Chinese Standard GB16806 as well as some bug fixing. 3 Versions and compatibility 3.1 AlgoWorks 3.1.1 Program and setup version The new AlgoWorks setup version for EP7F-Z2.2 is V1.63.1-000.
Versions and compatibility 3.2 Embedded software CS1140/45 3.2.1 Program and setup version The current embedded software setup version for EP7F-Z2.2 is 800. It is a full setup and other embedded software versions may be installed in parallel without problems. Please see document [1] and [2] for further information. 3.2.2 Program / site compatibility The embedded software version 800 is backwards compatible to older versions, but the customer side data has to be converted as well.
Versions and compatibility 3.2.3 Variants of embedded software There are two different variants of embedded SW: EPROM variants for the old HW types (E3X101, B3Q460/480/485, B3Q560, E3X120, E3H020) – FLASH variants for the new HW types (E3X102/103, B3Q660/661/680/685, B3Q565, E3H021) – For checksums of the different versions, please see the detailed documentation which is provided together with the embedded SW on the Service Technicians installation CD.
Versions and compatibility 3.3 BDVs JX_114x_800_01 3.3.1 Program and setup version The current BDV setup version for EP7F-Z2.2 is JX_800_01. It is a full setup and other BDV versions can be installed. Please see also documents [1] and [2] for further information. 3.3.2 Program / site compatibility The BDV versions JX_1140_800_01 and JX_1145_800_01 are backwards compatible to older versions, but the customer side data has to be converted.
AlgoWorks Software 1.60 (replaced by 1.63) 4 AlgoWorks Software 1.60 (replaced by 1.63) 4.1 Introduction / overview AlgoWorks V1.60 supports all new functions of the embedded software 790 and the BDV versions JX_114x_790_02. 4.2 Site Management The corresponding online help shows with the flash icons, which contents were changed or new. 4.3 Station Management The corresponding online help shows with the flash icons, which contents were changed or new. 4.4 Miscellaneous online helps 4.4.
AlgoWorks Software 1.63 5 AlgoWorks Software 1.63 5.1 Introduction / overview AlgoWorks V1.63 supports all new functions of the embedded software 800 and the BDV versions JX_114x_800_01. 5.2 Site Management The corresponding online help shows with the flash icons, which contents were changed or new. 5.3 Station Management The corresponding online help shows with the flash icons, which contents were changed or new. 5.4 Miscellaneous online helps 5.4.
AlgoWorks Software 1.63 5.5 Bug fixes / Work arounds Bug description Tracking no. FSP00009047 Hotline call none After a conversion of site data from EP5 to EP7F is carried out, which includes CPU overlapping remote transmission, the converter were not able to convert the data correctly because the necessary structure numbers are different between EP5 and EP7F.
AlgoWorks Software 1.63 Bug description Tracking no. FSP00011910 Hotline call none If an upload command were carried out on a CI1145 station the settings of the I/O types were wrong. Correction The bug has been fixed and the I/O types are correct now. FSP00022071 (FSP00022161) 56408 Hotline call (56123) If a consistency check were carried out on a Dual Core laptop it could happen that the tool was terminating. Tracking no.
Embedded Software 7.90 (replaced by 8.00) 6 Embedded Software 7.90 (replaced by 8.00) 6.1 Introduction / overview Embedded software version 790 supports all new functions of AlgoWorks version V1.60 and the BDV versions JX_114x_790_02. Only the Standard embedded software setup is available at the moment. The Asia version is not available yet. It will be provided later. Different embedded software setup packages can be installed in parallel. The embedded software version 7.
Embedded Software 8.00 7 Embedded Software 8.00 7.1 Introduction / overview Embedded software version 800 supports all new functions of AlgoWorks version V1.63 and the BDV versions JX_114x_800_01. Different embedded software setup packages can be installed in parallel. The embedded software version 8.00 replaces all other embedded versions, which were published before. Do not mix different embedded software versions at the same customer site.
Embedded Software 8.00 Bug description Tracking no. FSP00015627 Hotline call 43390 We have been informed that the performance of older EP5 sites is better than the performance of newer EP7F sites. Correction A first step of improvement has been done. The data transfer between CT-stations is related to two settings/conditions. Setting of 'LON CPU-overlapping' flag and connection of parallel indicators on a CT-station. Both setting/conditions reduce the performance of system.
BDVs JX_114x_790_02 (replaced by JX_114x_800_01) 8 BDVs JX_114x_790_02 (replaced by JX_114x_800_01) 8.1 Introduction / overview BDV versions JX_1140_790_02 and JX_1145_790_02 support all new functions of the AlgoWorks V1.60 and embedded software 790. The major changes compare to BDV JX_114x_780_04 (provided with EP7F-Z2.1 are: – – – – 8.
BDVs JX_114x_790_02 (replaced by JX_114x_800_01) 8.5 Changes in BDV online help The corresponding online help shows with the flash icons, which contents were changed or new. 8.6 Bug fixing 8.6.1 Wrong country default setting for MS9I I/O Module Bug description Tracking no. FSP00024718 Hotline call 82888 Belongs only to BDV J0_1145_780_03 country defaults (and earlier CI1145 versions). If you look at MS9i mod. device it has two child nodes, on input and one output. The input has I/O no.
BDVs JX_114x_800_01 9 BDVs JX_114x_800_01 9.1 Introduction / overview BDV versions JX_1140_800_01 and JX_1145_800_01 support all new functions of the AlgoWorks V1.63 and embedded software 800. The major changes compare to BDV JX_114x_790_02 are: – – – – – 9.
BDVs JX_114x_800_01 9.3 Changes in Country Defaults This chapter gives a short overview about the differences in Country Defaults between JX_114x_790_02 and JX_114x_800_01. Deleted devices types FDCO221 and FDCIO221 In earlier versions the device types FDCO221 and FDCIO221 were pre defined. Because such devices do not exist and there is no planning to do so, these device types have been deleted. 9.
Miscellaneous 10 Miscellaneous 10.1 Transponder FDCIO223 Restrictions Using special index version The Transponder FDCIO223 may only be used with index 41 or higher. Channels used as sounder lines Sounder tones are not synchronized between different Transponders devices on the same FDnet. However the two sounder lines on the same Transponder are synchronized. Channels used as standard outputs If the channels are defined as I/O’s, some settings about fail safe position can be set.
Update procedures 11 Update procedures For detailed information about the update procedure, please see document [1]. Back up 12 Please save the data before starting with update procedure. Documentation The following documents have been updated and published on Siemens Intranet.
Siemens Switzerland Ltd Building Technologies Group International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel. +41 41 – 724 2424 Fax +41 41 – 724 3522 www.siemens.com/buildingtechnologies Document no. A6V10081374_b_en Edition 11.2008 Manual CS11.