User Manual

instabus EIB
Technical Product Information
December 2007
Dual Sensor for Brightness and Temperature 5WG1 254-3EY02
AP 254/02
Siemens AG AP 254/02, 6 pages Technical Manual
Automation and Drives Group
Electrical Installation Technology © Siemens AG 2007 Update: http://www.siemens.de/installationstechnik
P.O. Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.13.2.11/1
Product and Applications Description
Functional description
The Dual Sensor AP 254/02 provides ambient light level
and outdoor temperature values. These values can be
sent onto the bus.
The device offers four universal channels (A, B, D, E)
and one solar protection channel C, which evaluate light
level and temperature for their configured function.
Each universal channel alternatively provides the follow-
ing threshold switches for control of switching, dimming,
and solar protection actuators based on ambient light
level and/or temperature:
threshold switch for light level
threshold switch for temperature
threshold switch for light level and temperature com-
bined
Dependent on whether the threshold condition is met or
not met a corresponding telegram is sent onto the bus
via the associated channel object. Additionally, a second
object can be activated as required to send a second
telegram.
Each universal channel can be deactivated by an asso-
ciated blocking object. For each universal channel if a
light level threshold is applied it may be set to the current
light level via an associated learning object.
Additionally, the device provides a solar protection
channel C for automatic control of solar protection equip-
ment. The automatic control can be started and stopped
via an object (sun control) or via a dusk/dawn ambient
light level threshold. Up to three light level thresholds
control the position (height and angle of slats) of the so-
lar protection blinds.
The light level thresholds may be set by sending a bus
telegram to an associated learning object. The solar pro-
tection channel can be deactivated by an associated
blocking object.
Function for blinds
:
When threshold 1 is exceeded the blind is moved down
via the first object (height) and the slats are moved into a
first position via the second object.
When threshold 2 is exceeded the slats are moved into a
second position. The height remains the same.
When threshold 3 is exceeded the slats are moved into a
third position. The height remains the same.
When the light level falls below any threshold the blind is
moved into the previous position and/or height. When
the light level falls below threshold level 1 the blind is
moved up.
Function for shutters / textile solar protection
:
When threshold 1 is exceeded the shutter is moved
down into a first position via the object “height”.
When threshold 2 is exceeded the shutter is moved
down into a second position via the object “height”.
When threshold 3 is exceeded the shutter is moved
down into a third position via the object “height”.
When the light level falls below any threshold the blind is
moved to the previous height. When the light level falls
below threshold level 1 the blind is moved up.
While automatically controlling solar protection equip-
ment fast changing sunshine conditions can lead to fre-
quent up and down movements of the solar protection
equipment. To avoid frequent up and down movement of
the solar protection the parameter “Reaction to sun con-
trol ON” can be set to “move up & sun control once”. The
behaviour of the blinds and shutters changes as follows.
Function for blinds (singular automatic sun control)
:
When threshold 1 is exceeded the blind is moved down
via the first object (height) and the slats are moved into a
first position via the second object. The blind stays at
this height all day long. The blind is moved only at dusk
or via the object for automatic sun control. Only the slats
are adjusted dependent on the current light level.
When threshold 2 is exceeded the slats are moved into a
second position. The height remains the same.
When threshold 3 is exceeded the slats are moved into a
third position. The height remains the same.
When the light level falls below any threshold the slats
are moved into the previous position.
Function for shutters / textile solar protection (singular
automatic sun control):
When threshold 1 is exceeded the shutter is moved
down via the object (height).
When threshold 2 is exceeded the shutter is moved into
a second position via the object (height).
When threshold 3 is exceeded the shutter is moved into
a third position via the object (height).

Summary of content (6 pages)