User Manual

GAMMA instabus
Technical Product Information
February 2019
Weather Station (GPS) AP 257/22 5WG1 257-3AB22
Siemens Switzerland Ltd DS01 Update: http://www.siemens.de/gamma-td
Building Technologies Division
International Headquarters Siemens AG 2019
Theilerstrasse 1a Subject to change
CH-6300 Zug 2
Installation Instructions
If the weather station has been damaged, it must not be
commissioned.
V
WARNING
The device must be mounted and commissioned by an
authorised electrician.
For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical Specifications
Sensors
Wind sensor:
Measuring range: 0 ... 35 m/s,
Resolution: 0.1 m/s
precision at ambient temperature -20…+50°C:
±22% of measured value with air flow from 45…315°
±15% of measured value with air flow from 90…270°
(air flow onto the front equals 180°)
Brightness sensor:
Measuring range: 0 ... 150.000 lux,
Resolution at: 0 ... 120 lux 1 lux
121 ... 1.046 lux 2 lux
1.047 ... 52.363 lux 63 lux
52.364 ... 150.000 lux 423 lux
Precision: ±20% at 0 lx … 10 klx
±15% at 10 klx 150 klx
Temperature sensor:
Measuring range: -30 ... +50 °C,
Resolution: 0.1 °C
Precision: ±0,5°C at +10…+50°C,
±1°C at -10…+10°C,
±1,5°C at -25…-10°C
Rain sensor:
Heating: approx. 1.2 W
Voltage supply
Bus voltage: via the bus line
KNX bus current: 9 mA
Auxiliary power sensor electronics:
AC 20 V (AC 12...28V) 50/60 Hz or
DC 24 V (DC 12...40V) max. 185 mA at DC 12V, residu-
al ripple < 10%, max. permissible cable length 100 m
Power consumption: max. 2.3 VA
Operator elements
1 commissioning button: for switching over between
normal mode / addressing mode
Display elements
1 red LED: for display of normal mode / addressing
mode (off / on)
1 red LED: as control display for GPS reception
Connections
Voltage supply: plug terminals for solid conductors or
finely stranded conductors 0.5 ... 1.5mm²
Bus connection: screwless bus terminal,
0.6... 0.8 mm single-wire, insulation strip length 5
mm.
Mechanical data
housing: plastic
Dimensions :
approx. 118 mm x 96 mm x 77 mm (L x W x H)
Weight: approx. 170 g
Fire load: approx. 5360 kJ
Mounting: Mast or wall mounting
Electrical safety
Degree of pollution (according to IEC 60664-1): 2
Type of protection (according to EN 60529): IP 44
Overvoltage category (according to IEC 60664-1): III
Bus: safety extra-low voltage (SELV) DC 24 V
Device complies with EN 50090-2-2
EMC requirements
complies with EN 50090-2-2
Environmental conditions
Climatic conditions: EN 50090-2-2
Ambient temperature operating: - 30 ... + 50 °C
Ambient temperature non-op.: - 30 ... + 70 ° C
Relative humidity (non-condensing): 5 % … 93 %
Markings
KNX EIB
CE mark
complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations