Installation Instructions
Installation Instructions
Document No. 553-148
January 27, 2009
UC/FLNC Migration Backplane Kit
Siemens Building Technologies, Inc. Page 1 of 2
Product Description
The DIN Migration kit allows replacement of an
existing Unitary Controller or Floor Level Network
Controller while keeping the same enclosure and
field wiring.
This kit includes the following components:
One perforated backplane
Accessory kit that includes the following:
One 12-inch DIN rail.
Two 9.5-inch wire tie bars.
One 16 AWG Green/Yellow wire for
connecting the PXC Compact, P1 BIM,
or PXC Modular protective ground to the
service box earth ground.
One UC Bezel Cover Plate.
CAUTION:
Use of a backplane without the UC or
FLNC enclosure voids all UL, CSA, and
FCC approvals, as well as European EMC
and LVD compliance.
Product Numbers
1
PXA-UCKIT
UC/FLNC DIN Migration
Backplane Kit
535-104
(AM-2483-OA)
UL Listed Class 2 plug in
transformer with 120 Vac
50/60 HZ primary and 24Vac
20VA secondary (for FLNC
only)
545-712
MMI Extension Cable
1. Required for Smoke Control Installations.
Danger/Warning/Caution Notations
DANGER:
Electric shock, death, or severe
property damage may occur if
you do not follow procedures as
specified.
WARNING:
Personal injury or property
damage may occur if you do not
follow procedures as specified.
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow procedures as specified.
Required Tools
Wire ties
Number 2 Phillips screwdriver
Small straight-blade screwdriver
11/32
nd
socket and drive
Wire Strippers
Digital Multimeter
Expected Installation Time
10 minutes for removal of backplane
10 minutes for installation of backplane
Prerequisites
Plan out field panel migration strategy
Order appropriate hardware required
Establish a shut-down procedure with the
building owner