Installation Instructions
Installation Instructions
Document No. 553-156
October 4, 2017
PXA-DIN16KIT For Seismic Installation
Item Number: 553-156, Rev. AA Page 1 of 4
Product Description
PXA-DIN16KIT provides installation method for DIN
mounted energy management components in Seismic
Certified enclosures other than Type 1 PX Series.
Obtain Seismic Sticker from CPS Product Manager.
PXA-DIN16KIT consists of (4) 16.25” Pre-galvanized
steel DIN rails meeting EN 60715 TH 35-7.5-1 mm,
see Figure 1 and (12) #8-18 x 3/8” pan head Type B
thread tapping zinc plated steel SEMS locking screws.
PXA-DIN16KIT when installed per this instruction on a
rigidly mounted subpanel inside a Type 1 or higher
Seismic Certified enclosure is certified to comply with
IBC 2009 and CBC 2010 and may be used to mount
List of Equipment/Components in following OSHPD
Special Seismic Certification Preapproval (OSP).
∂ OSP-217-10 and OSP-218-10
Product Numbers
PXA-DIN16KIT FOUR 16.25" DIN RAILS
Optional Product Numbers
PXA-TIEBARKIT Tie Bar Kit (4) 9.5”, (4) 4.5”,
(12) ¾” TY-wrap, (16) screws
PXA-SB115V192VA PX Series Service Box
PXA-SB115V384VA PX Series Service Box
PXA-SB230V192VA PX Series Service Box
PXA-SB230V384VA PX Series Service Box
PXA-SW192VA PX Series Side Wall 192VA
PXA-SW384VA PX Series Side Wall 384VA
Instructions for optional products: 553-131 & 553-135.
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedure as
specified.
Expected Installation Time
30 minutes
Required Tools and Materials
∂ Medium Phillips screwdriver
∂ 7/16-inch nut drivers (bolts and SB nuts)
∂ Three corrosion resistant 1/4” - 20 x ½” bolts
and flat washers (used with SB lock nuts)
Prerequisites
CAUTION:
Anchorage is not preapproved for Seismic
Certification and must be approved by the
Inspector of Record before installation.
Seismic Certification Preapproval requires:
∂ Enclosure used must be included in
Certified List of Equipment and
Components of an OSHPD Special
Seismic Certification Preapproval
(OSP), example for Air Handler.
∂ Enclosure must be mounted on a wall
(rigid) or HVAC equipment wall
designated (rigid) with four corrosion
resistant 1/4” - 20 bolts minimum, flat
washers and nuts.
∂ Subpanel must be of rigid mount type
specified for use in Enclosure.
General use:
∂ Enclosure of type required for the
installation environment.
∂ Enclosure mounted with clearance to
open door and door off if needed.
∂ Conduit run/sealed. Wires pulled
through enclosure and labeled.
∂ Enclosure must be mounted at least 12
feet (3.7 m) away from devices that
can generate Radio Frequency
Interference (RFI), such as Electro-
pneumatic devices (EPs), relays, and
walkie-talkies.
∂ Enclosure must be mounted at least 5
feet (1.5 m) away from 100 kVa or
larger motors and variable frequency
drives (VFD).