Installation Instructions

Installation Instructions
Document No. 553-131
August 16, 2013
PX Series
Service Box Assemblies
Siemens Industry, Inc. 553-131 (CA) Page 1 of 4
Product Description
The PX Series Service Box Assemblies transform
115 Vac or 230 Vac to 24 Vac that power HVAC
control components. The 192 VA service boxes
mount directly inside a 19-inch or 34-inch PX Series
Enclosure or as a replacement in older MEC
Enclosures. The 384 VA service boxes provide
additional power for larger systems and mount only
in the 34 inch PX Series Enclosure. The service
boxes are Smoke Control and Energy Management
listed when installed per this instruction.
The service box assemblies consist of:
Chassis for mounting inside enclosure
Transformer for converting either 115 Vac
or 230 Vac to 24 Vac sized for either 192 VA
or 384 VA
ON/OFF Circuit breaker for transformer
Two Class 1 power limited 24 Vac outputs
including one terminal for earth ground for
use inside enclosure only
One Class 2 output with circuit breaker to
distribute up to 96 VA for use outside the
enclosure
Duplex Service Outlet (115 Vac models
only)
Wire cover for field connections
Product Numbers
PXA-SB115V192VA Service Box 115V, 24 Vac,
50/60 Hz, 192 VA
PXA-SB115V384VA Service Box 115V, 24 Vac,
50/60 Hz, 384 VA
PXA-SB230V192VA Service Box 230V, 24 Vac,
50/60 Hz, 192 VA
PXA-SB230V384VA Service Box 230V, 24 Vac,
50/60 Hz, 384 VA
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not perform a
procedure as specified.
CAUTION:
Equipment damage or loss of
data may occur if you do not
perform a procedure as
specified.
Required Tools and Materials
Medium Phillips screwdriver
11/32-inch nut driver
7/16-inch nut driver
Expected Installation Time
15 Minutes
Prerequisites
Enclosure(s) installed.
AC power brought to enclosure(s) and
power turned OFF at the circuit breaker.
If using optional TX-I/O Bus (not available
on all hardware), it is pulled between
enclosures using single 2 twisted pair (TP)
or two 1 TP wire tied together. See TX-I/O
Bus steps for maximum length by wire
gauge.
Smoke Control Application
Requirements
UL864 and NFPA92A compliant installations require
the 115V or 230V PX Series Service Box Assembly
installed inside the 19-inch or 34-inch PX Series
Enclosure Assembly (PXA-ENC19 or PXA-ENC34).
For more information, see PX Series Enclosure
Assemblies Installation Instructions (553-130).
For smoke control installations, the 24 Vac Actuator
Output is a supplementary circuit intended for
general HVAC equipment only. It can not power
smoke control devices.
Optional: See the Field Purchasing Guide for
ordering the relay required for Smoke Control listing
if a TX-I/O Bus is powered from multiple service
boxes. (TX-I/O Bus not available on all hardware.)
RIB2401C UL864 Listed Relay, SPDT 24 Vac 10A