Installation Instructions

Installation Instructions
Document No. 586-136
December 17, 2003
Modular Equipment Controller (MEC)
Enclosure
Item Number: 586-136-02, Rev. 010 Page 1 of 4
Product Description
The Modular Equipment Controller (MEC) enclosure
(Figure 1) protects MECs against airborne
contaminants such as lint, dust, dirt, water seepage,
dripping, and external condensation of non-corrosive
liquids.
The MEC panel is factory-equipped with the
following:
Factory-installed backplane assembly which
includes wire tie down rails
Wall template
Label pouch
Product Numbers
549-504 Small MEC Enclosure
549-505 Large MEC Enclosure
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if you do not
follow the procedure as
specified.
Required Tools and Materials
Adjustable wrench or pliers
Electric drill
Greenlee punch
Hammer
Level
Marker
Screwdrivers, small and medium Phillips-
head
Tape measure
Tie-wraps
Wire stripper/side cutters
To mount on concrete or masonry:
1/2 inch (12.7 mm) drill bit
Four lead wall anchors
Prerequisites
CAUTION:
Enclosure must be mounted on a non-
vibrating surface, at least 12 feet (3.65 m)
away from large motors and radio
equipment.
Under no circumstances should the
enclosure be mounted on ductwork or
HVAC equipment.
Expected Installation Time
30 minutes
Figure 1. MEC Enclosures.