Application

Sequence of Operation
Application Notes
12
Siemens Industry, Inc. Application Note, App 2521 140-1218
2015-05-06
CLG FLOW MAX
5. Motor setup information may be incorrect. Check the values of the following points
and correct as needed:
MTR SETUP
MTR1 TIMING
DMPR ROT ANG
6. The box may not have been balanced correctly. Contact your local Siemens
Industry representative.
7. The air velocity sensor may need calibration. Set CAL AIR to YES to run the
calibration sequence. When CAL AIR returns to NO, indicating that the sequence is
finished, run the checkout procedure again to see whether the problem has been
corrected.
Controller could not reach CLG FLOW MAX or aboveCHK STATUS =
16
1. Check for the problems described immediately above for CLG FLOW MIN.
2. The box may be starved for air, because either the central air-handling unit is off or
there is low duct static.
Controller did not read low (zero) flow when damper closedCHK
STATUS = 32
1. Check for the problems described above for CLG FLOW MIN.
2. The damper shaft may not be secured correctly to the actuator so that when the
actuator is fully closed, the damper does not completely shut off airflow.
3. Airflow calibration (at zero) may need to be performed ensuring the damper is fully
closed and/or the air handling unit is off.
Application Notes
If temperature swings in the room are excessive or there is trouble maintaining the
setpoint, the cooling loop must be tuned. If FLOW is oscillating while FLOW STPT
is constant, the flow loop requires tuning.
The controller, as shipped from the factory, keeps all associated equipment OFF.
For more information, contact your local Siemens Industry representative.