Commissioning Instructions

Before You Begin
Setting Room Temperature Setpoints
7
Siemens Industry, Inc. Start-up Procedures 140-1199
Restricted 2015-05-06
CAL SETUP Options.
CAL SETUP
(value)
Description
command before beginning the calibration routine.
2 Calibration occurs immediately after the override switch is pressed.
4
(factory default
value)
Calibration occurs on the time interval set in the point CAL TIMER.
Example:
If CAL TIMER = 12, then the calibration period is 12 hours.
Actual calibration is subject to a time delay based on the value of CTLR
ADDRESS. See the example in Option 1 in this table.
Since these are additive values, options can be combined by summing their numbers.
For example, to calibrate in Options 1 and 2, set CAL SETUP to
.
Setting Room Temperature Setpoints
Day (or OCC) cooling setpoint: DAY CLG STPT or OCC CLG STPT
Day (or OCC) heating setpoint: DAY HTG STPT or OCC HTG STPT
Night (or UOC) cooling setpoint: NGT CLG STPT or UOC CLG STPT
Night (or UOC) heating setpoint: NGT HTG STPT or UOC HTG STPT
1. If the room temperature sensor has a setpoint dial that will be used, set STPT DIAL
to YES. Otherwise, leave STPT DIAL to NO.
Set RM STPT MIN and RM STPT MAX for the minimum and maximum
allowable room temperature setpoint values, respectively. Valid values range
from 55° to 95°F (13° to 35°C). Default values are 55°F (13°C) for RM STPT
MIN and 90°F (32°C) for RM STPT MAX.
2. Setpoint dial configured with a heating/cooling deadband (default).
To allow the controller to operate with a heating/cooling deadband (functioning
the same as provided when the setpoint dial is not present), use the following
configuration:
Set the DAY HTG STPT less than the DAY CLG STPT by the deadband (or
zero energy band) that is desired. (For example, DAY HTG STPT = 70°F; DAY
CLG STPT = 74°F, providing a deadband of 4 degrees). Only the difference
between these values is used to determine What setpoint will be used.
As described below, the setpoint(s) for heating/cooling will be 1/2 of the
deadband above or below the setpoint dial value.
When HEAT.COOL equals HEAT, then:
CTL STPT will equal RM STPT DIAL 0.5 * (DAY CLG STPT DAY HTG
STPT) and will be limited by RM STPT MIN and RM STPT MAX.
When HEAT.COOL equals COOL, then:
CTL STPT will equal RM STPT DIAL + 0.5 * (DAY CLG STPT DAY HTG
STPT) and will be limited by RM STPT MIN and RM STPT MAX.
NOTE: A space where the deadband is used can be more energy efficient than
a space where the deadband is not being used.
3. Setpoint dial configured for zero heating/cooling deadband.