Installation Instructions
Document No. 540-569
Installation Instructions
July 15, 2009
Accessories
540-658P25 Low cost temporary temperature
sensor that enables space control if
the permanent room or duct sensor
is not installed.
Parts for Smoke Control Compliance
540-155K
Smoke Control Listed Small
Equipment Controller Enclosure
550-002K
Smoke Control Listed Large
Equipment Controller Enclosure
ZBX-XXXX
a
Smoke Control Listed Large
Equipment Controller Enclosure
5041MWCB UL Listed Class 2 transformer with
120/240/277/480 Vac 50/60 HZ
0.4A primary w/ hub and 24Vac
50VA secondary w/ hub and circuit
breaker
10041MWCB UL Listed Class 2 transformer with
120/240/277/480 Vac 50/60 HZ
0.5A primary w/ hub and 24Vac
96VA secondary w/ hub and circuit
breaker
KELE AM-2483-OA UL Listed Class 2 Transformer
with primary 120V 60 HZ 0.2A
secondary 24 Vac 30 VA
529-804
Receptacle assembly consisting of
aULListed2x4junctionboxand
UL Listed receptacle
a. Enclosure part number ZB-X-XXXX, where the first X
can be 9 or any letter from A to N represents the type of
TEC module installed/to be installed in the enclosure, and
XXXX can be any 4 alphanumeric characters represent
the TEC HVAC application.
For smoke control application, primary
rating is only 120V/ 60 Hz.
Parts for CE Compliance:
550-705
Clamp-on ferrite filter (10 pack)
588-100 series
Approved 2-RJ11 RTS cable in 25’,
50’, or 100’ (7.6-m, 15.2-m, 30.48-m).
Warning/Caution Notations
WARNING:
Personal injury/loss of life may occur if you
do not follow the procedures as specified.
CAUTION:
Equipment damage or loss of data may
occur if you do not follow the procedures
as specified.
Expected Installation Times
10 minutes.
Required Tools and Materials
• Electro-Static Discharge (ESD) wrist strap
• Flat-blade screwdriver (1/8-inch blade width).
•Smallflat-blade screwdriver
• Cordless drill/driver set
• 1/4-inch (6.35 mm) hex nut bit
Prerequisites
• Dual Duct with one AVS installed
• 24 Vac Class 2 power source
• Supply power to the unit is OFF
• If required, controller enclosure installed
• Room temperature sensor installed (optional).
(If desired, a low-cost temporary temperature
sensor is available that plugs into the RTS
port of the TEC (P/N 540-658P25), providing
temperature input and actual space control
until the permanent room or duct sensor is
installed.)
Instructions
The installation is complete.
All wiring must conform to NEC and local
codes and regulations.
Page 2 of 12 Siemens Building Technologies, Inc.