Point Database
Overview
This chapter presents a description of the Heat Pump Controller—Multi-Stage point database
including point descriptors, point addresses, and a listing of applications in which each point
is found.
Description Address Application Description
CTLR ADDRESS 01 2273, 2274, 2290 ldentifies the controller on the FLN trunk.
APPLICATION 02 2273, 2274, 2290 Identification number of the program running in the
controller.
Valid input: 2273, 2274, 2290
RETURN DELAY 03 2273, 2274 Amount of time the heat pump will remain off after a return
from power failure.
ROOM TEMP 04 2273, 2274, 2290 Actual reading from the room temperature sensor.
HEAT.COOL 05 2273, 2274 Current mode of operation for applications that can be either
a heating mode or a cooling mode.
DAY CLG STPT 06 2273, 2274 Temperature setpoint in degrees that the controller
maintains during day periods in cooling mode if a room
temperature sensor setpoint dial is not present or is not
used. See STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9°to 35°C)
DAY HTG STPT 07 2273, 2274 Temperature setpoint in degrees that the controller
maintains during day periods in heating mode if a room
temperature sensor setpoint dial is not present or is not
used. See STPT DIAL (Point 14).
Valid entry range: 48° to 95°F (9° to 35°C)
NGT CLG STPT 08 2273, 2274 Temperature setpoint in degrees that the controller
maintains during night periods in cooling mode.
Valid entry range: 48° to 95°F (9° to 35°C)
NGT HTG STPT 09 2273, 2274 Temperature setpoint in degrees that the controller
maintains during night periods in heating mode.
Valid entry range: 48° to 95°F (9° to 35°C)
DMPR MlN POS 10 2273, 2274 Minimum position the damper will be commanded to during
day mode.