Installation Instructions

Document No. 540-568
Installation Instructions
April 10, 2008
24V 60 HZ 42 VA
Digital Output (DO) Electrical Ratings:
Transformer P/N 5041BCWB: maximum
6VA per DO/ maximum 30 VA total.
Transformer P/N 10041BCWB: maximum
6VA per DO/ maximum 36 VA total.
Transformer P/N AM-2483-OA: maximum
6VA per DO/ maximum 16 VA total.
3. The room temperature sensor (RTS) is installed
inthesameroomastheTEC.
4. Connection from the TEC to the APOGEE eld
panel is maximum 4000 feet, 24 AWG minimum.
5. Wiring Range:
Transformer: primary 14 AWG
24 Vac Input Power: 14 to 18 AWG
DO:AI:18to20AWG
•DI:18AWG
LAN:20to24AWG
•RST:24AWG
6. Refer to the following documents when used
conguring for smoke control application:
125-1806: Smoke Control Systems
Application and Engineering Manual
125-1816: Smoke Control System
Application Guide
125-1817: NFPA and UL Standards
Relevant to Smoke Control System
Application Guide
CE Compliance
If CE compliance is required, a ferrite lter must be
placed approximately 1–2 cm from the end of the
cable being shielded (RTS cable and the point wiring
for AI3) (Figure 4).
TEC0320R3
1- 2 cm
1
Place the filter 1-2 cm
from the end of the cable
or wiring to be shielded.
2
Wind the cable tightly
twice around the filter.
3
Close the filter and wrap
with a zip tie.
Figure 4. Ferrite lter(s) for CE Compliance.
Page 4 of 8
Siemens Building Technologies, Inc.