desired, the operator may adjust the room
temperature setpoints and other parameters. The
controller is designed for operation and modification
without vendor assistance.
Hardware
Controller Board
The TEC Unit Vent Controller consists of an electronic
controller assembly.
This controller provides all wiring terminations for
system and local communication and power. The
cable from the room sensor (purchased separately)
connects to an RJ-11 jack on the controller. All other
connections are removable terminal blocks. The
controller assembly is mounted on a plastic track that
mounts directly on the unit ventilator. An optional
enclosure (P/N 550-002) protects the controller
assembly.
The controller interfaces with the following external
devices:
0-10V Damper Spring Return Actuator
0-10V Valve Spring Return Actuator
Temperature sensors (room and averaging)
Portable Operator's Terminal
DDC Automation Systems
Digital input devices (dry contacts from motion
sensors, alarm contacts)
Digital output devices (fan, stages of electric heat,
DX cooling, 2 position valves)
Room Sensor
The room sensor connection to the controller board
consists of a quick-connect RJ-11 jack. This
streamlines installation and reduces controller start-up
time.
Unit Vent Controller
Specifications
Dimensions 4-1/8" W × 11-1/4" L × 1-1/2" H
Weight approx. 3 lbs (1.35 kg)
Controlled Temperature
Accuracy, Heating or
±1.5°F (0.9°C)
Cooling
Power Requirements
Operating Range 18 to 28 Vac, 50 or 60 Hz
Power Consumption 4.4 VA (plus 12 VA per DO)
Inputs
Analog 1 room temperature sensor
(spare temp and set point)
1 voltage (0-10Vdc)/Current 4-
20mA switch selectable
Digital 2 dry contacts (DI 2 and DI 4)
Outputs
Analog 3 0-10 Vdc, 5mA maximum
Digital 8 DO 24 Vac optically isolated
solid state switches @ 0.5 amp
Communications
Remote 9600 bps to 76800 bps LAN
Trunk
Local WCIS
Ambient Conditions
Shipping & Storage
Temperature
-13°F to 158°F (-25°C to 70°C)
Operating Temperature 32°F to 122°F (0°C to 50°C)
Humidity Range 5 to 95% rh (non-condensing)
Agency Listings
UL Listing UL 916, PAZX
cUL Listed Canadian Standards C22.2 No.
205-M1983, PAZX7
FCC Compliance 47 CFR Part 15, Class A