Installation Instructions

Installation Instructions
Document No. 129-145
November 18, 2013
Room Pressure Monitor
Item Number 129-145, Rev. EA Page 1 of 11
Product Description
The Room Pressure Monitor (RPM) is designed for
critical low differential pressure applications that
require stringent pressure monitoring and alarming.
The unit can be configured to monitor positive or
negative pressure in protected environments and
hospital isolation rooms per CDC guidelines.
Contents
Qty Description
1 Room Pressure Monitor Assembly
2 Strain relief tubing assembly
3 6-32 × 1/2" mounting screws (for connecting the
monitor base to the plaster ring)
Intended Use
The SRPM is designed for indoor use only to
monitor critical environments by providing differential
pressure indication. Typically, this is between a
monitored room and a reference space such as a
corridor or ante room. The unit also provides
monitorin, alarm and communications functions.
Installation must be indoors, Pollution Degree 2,
Installation Category II.
Typical Applications
Surgical suites
Intensive care isolation rooms
Research laboratories
Pharmaceutical facilities
Organic laboratories
Animal research facilities
Expected Installation Time
20 minutes
Product Numbers
Product
Number
WC Protocol FS
547-101A +/- 0.05" WC (12.5 Pa) P1 0.5%
547-102A +/- 0.1" WC (25 Pa) P1 0.5%
547-103A +/- 0.25" WC (62.5 Pa) P1 0.5%
547-104A +/- 0.50" WC (12 5Pa) P1 0.5%
547-105A +/- 1.0" WC (250 Pa) P1 0.5%
547-106A +/- 2.55" WC (625 Pa) P1 0.5%
547-107A +/- 5.0" WC (1250 Pa) P1 0.5%
547-101B +/- 0.05" WC (12.5 Pa) P1 0.25%
547-102B +/- 0.1" WC (25 Pa) P1 0.25%
547-103B +/- 0.25" WC (62.5 Pa) P1 0.25%
547-104B +/- 0.50" WC (12 5Pa) P1 0.25%
547-105B +/- 1.0" WC (250 Pa) P1 0.25%
547-106B +/- 2.55" WC (625 Pa) P1 0.25%
547-107B +/- 5.0" WC (1250 Pa) P1 0.25%
547-201A +/- 0.05" WC (12.5 Pa) BACnet 0.5%
547-202A +/- 0.1" WC (25 Pa) BACnet 0.5%
547-203A +/- 0.25" WC (62.5 Pa) BACnet 0.5%
547-204A +/- 0.50" WC (12 5Pa) BACnet 0.5%
547-205A +/- 1.0" WC (250 Pa) BACnet 0.5%
547-206A +/- 2.55" WC (625 Pa) BACnet 0.5%
547-207A +/- 5.0" WC (1250 Pa) BACnet 0.5%
547-201B +/- 0.05" WC (12.5 Pa) BACnet 0.25%
547-202B +/- 0.1" WC (25 Pa) BACnet 0.25%
547-203B +/- 0.25" WC (62.5 Pa) BACnet 0.25%
547-204B +/- 0.50" WC (12 5Pa) BACnet 0.25%
547-205B +/- 1.0" WC (250 Pa) BACnet 0.25%
547-206B +/- 2.55" WC (625 Pa) BACnet 0.25%
547-207B +/- 5.0" WC (1250 Pa) BACnet 0.25%
Warning/Caution Notations
WARNING:
Personal injury/loss of life may
occur if you do not follow the
procedures as specified.
CAUTION:
Equipment damage, or loss of
data may occur if you do not
follow the procedures as
specified.