Installation Instructions
Document No. 129-145
Installation Instructions
November 18, 2013
FLN Set-up
FLN hardware is implemented as isolated RS485.
Wire to Connector J2, labeled FS-485. Connect tx
line to +(A), rx to –(B) and ground wires to S.
Connect Shields together with wire nut.
The installation is now complete.
Start-up and Operation
The RPM is designed with as an easy-to-use,
intuitive, touch screen interface. In its normal
(default) state the Monitoring Screen displays the
actual room static pressure, and a slider bar shows
the actual pressure relative to the alarm limits. The
RGB backlight is used to indicate the condition of
the room. The buttons at the bottom of the screen
give you access to the functions that can be
performed.
Siemens Industry, Inc. Page 5 of 11
Power-Up
Apply power and observe the welcome screen and
subsequent transition to the pressure monitor
screen. The actual room static pressure is shown as
a number in the center of the LCD and visually as a
moving bar indicator operating between the preset
alarm units. The vertical bar is an indicator of the
pressure.
Monitoring Screen
Button Description
Silence Shuts off alarm.
Menu Provides access to Main Menu
functions.
Reset Resets the unit in Latched mode.
The following screens are configuration screens that
can be configured so that Password protection is
required to make changes. If no entry is made to the
screen, the unit will return to the default screen after
approximately one minute.
Main Menu Screen
Button Description
Unit Sets up supervisor password, output,
engineering units, and display averaging.
Room Sets up high and low pressure limits to
monitor a positive, negative, or neutral
room. Operator password setup.
Alarm Sets up latch alarm, audible alarm, door
alarm input, mute time out, alarm delay,
and volume.
BACnet/
P1FLN
Configures BACnet/P1FLN
Communications.
Self-test Identifies product model and software
version, and serial number. Verifies
memory and performs alarm test.
Calibration Performs zero and span calibration.
Back Returns to monitoring screen.