You can also perform a self-test of the unit to verify
that the data in the protected area of the EEPROM
memory hasn’t been corrupted, and test the alarm to
verify the sound level and alarm setup.
Press the Self Test button to initiate an EEPROM
memory checksum test sequence.
Press Alarm Test to test beeper, visual Red LED
Alarm, and relay output. This can be used to verify
the system in Alarm Mode.
Page 8 of 11 Siemens Industry, Inc.
Press Cancel Test to stop the alarm test.
Press Exit to return to the Main Menu.
BACnet Setup Screen
1. Enable the MAC address enable switch (S1)
on the DIP switch by pushing it to the right.
2. Set Device Address – Enter the address of the
device
3. Select Baud Rate – Press the correct baud
rate button (9600 to 76800).
4. Press Save & Exit to save settings, or Cancel
to cancel the setting changes.
5. When complete, disable the BACnet setup by
moving the DIP switch position 1 to Off (left)
position.
6. If the unit will be at the end of the line, the pull
up resistor can be enabled by pushing position
3 to On.
7. The termination resistor can be inserted by
pushing position 4 switch to On.
8. The pull down resistor can be enabled by
turning position 5 to On.
9. Press Save & Exit. After the unit returns to the
Main Menu screen, disconnect the power to the
unit, then reconnect to boot-up with the proper
MAC Address and Device Instance.
DIP Switch
Position
Function
1 MAC address enabled
2 Not Used
3 Pull Up Resistor
4 Termination Resistor
5 Pull Down Resistor
Contact Siemens Industry, Inc. for information on
Point list and PICS and BIBBS statements.
FLN Setup Screen
To set up FLN communications:
1. Set Device Address – Enter the address of the
device.
2. Select Baud Rate – Press the correct baud rate
button (4800 to 19200).
3. Press Save & Exit to save settings, or Cancel
to cancel the setting changes.
Pressure Monitoring Screens